UPS Electrical Characteristics
Refer to additional circuit breaker notes in
3.2.7 - Accessory Fuses and Back-Feed Breaker Wiring
NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be
provided for AC input, DC input and AC output. Recommended cable sizes are suitable for operation at a
maximum temperature of 104°F (40°C).
Table 15
UPS currents and terminals—Input (for single-input unit, 208V operation)
Unit
Rating
Nominal
Input Current
Maximum
Input Current
OCP Device
Rating
Bolt Size
75°C Wire
Current, Total
Copper
Wire
Aluminum
Wire
20
59
68
90
M12
115
(1) #2
(1) 1/0
40
119
136
175
M12
230
(1) 4/0
(2) 1/0
60
178
205
300
M12
400
(2) 3/0
(2) 4/0
80
237
273
350
M12
460
(2) 4/0
(2) 300 kcmil
100
297
341
450
M12
610
(2) 350
(2) 400 kcmil
Table 16
UPS currents and terminals—Input (for dual-input unit only, 208V operation)
Unit
Rating
Nominal
Input Current
Maximum
Input Current
OCP Device
Rating
Bolt Size
75°C Wire
Current Total
Copper
Wire
Aluminum
Wire
20
59
68
90
M12
115
(1) #2
(1) 1/0
40
119
136
175
M12
230
(1) 4/0
(2) 1/0
60
178
205
300
M12
400
(2) 3/0
(2) 4/0
80
237
273
350
M12
460
(2) 4/0
(2) 300 kcmil
100
297
341
450
M12
610
(2) 350
(2) 400 kcmil
Table 17
UPS currents and terminals—Bypass input (for dual-input units, 208V operation)
Unit
Rating
Nominal
Input Current
OCP Device
Rating
Bolt Size
75°C Wire
Current, total
Copper
Wire
Aluminum
Wire
20
56
70
M12
115
(1) #2
(1) #2
40
111
150
M12
175
(1) 3/0
(1) 4/0
60
167
225
M12
285
(1) 300
(2) 2/0
80
222
300
M12
400
(2) 3/0
(2) 4/0
100
278
350
M12
460
(2) 4/0
(2) 300 kcmil
Table 18
UPS currents and terminals—Output 208V
Unit
Rating
Nominal Output
Current
OCP Device
Rating
Bolt
Size
75°C Wire
Current, total
Copper
Wire
Aluminum
Wire
20
56
70
M12
115
(1) #2
(1) #2
40
111
150
M12
175
(1) 3/0
(1) 4/0
60
167
225
M12
285
(1) 300
(2) 2/0
80
222
300
M12
400
(2) 3/0
(2) 4/0
100
278
350
M12
460
(2) 4/0
(2) 300 kcmil
Summary of Contents for Liebert EXM