22
10: Acceptable high voltage for ECO mode
Interface
Setting
Parameter 2:
High voltage point in ECO mode. The setting
range is from 5% to 10% of the nominal voltage.
11: Acceptable low frequency for ECO mode
Interface
Setting
Parameter 2:
Low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
12: Acceptable high frequency for ECO mode
Interface
Setting
Parameter 2:
High frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
13: Phase auto adapt enable/disable
Interface
Setting
Parameter 2:
Enable or disable phase auto adapt function. You
may choose following two options:
DIS:
disable phase auto adapt function.
Then,
the UPS only can
accept one condition which the phase difference of L2 and L1 is
120º and phase difference between L3 and L2 is 120º.
ENA:
enable phase auto adapt function. Then, the UPS can
accept either inputs of L1, L2, L3 in the same phase or the phase
difference between L2 and L1 with 120º, L3 and L2 with 120ºor
phase difference between L2 and L1 240º, and L3 and L2 with
240º.
14: Bypass mode forbidden/allowed
Interface
Setting
Parameter 2: Allow or forbidden bypass mode
FBD:
Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
OPN:
Bypass allowed. When selected, UPS will run at Bypass
mode depending on the setting of “Switch off Bypass mode
enable/disable”