8
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage setting
You may choose the following output voltage in parameter
2:
200:
presents output voltage is 200Vac
208:
presents output voltage is 208Vac
220:
presents output voltage is 220Vac
230:
presents output voltage is 230Vac (Default)
240:
presents output voltage is 240Vac
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2:
Enable or disable converter mode. You may
choose the following two options:
CF ENA:
converter mode enable
CF DIS:
converter mode disable (Default)
03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50:
presents output frequency is 50Hz (Default)
BAT 60:
presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50:
presents output frequency is 50Hz (Default)
CF 60:
presents output frequency is 60Hz
04: ECO enable/disable
Interface
Setting
Parameter 2:
Enable or disable ECO function. You may
choose the following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)