LIEBERT® GXT5™ UPS HV GXT5‑8000/10KHVRT5UXLN

Quick Installation Guide

  

SL-70529_REV0_11-19

 

For proper ventilation, leave four 

inches clearance on all sides of 

the UPS.
The input outlet should be 

nearby and easily accessible.

3.  Installing the UPS

The UPS and optional External 

Battery Cabinets may be 

installed in either a tower or rack 

configuration. For tower 

installation, assemble and attach 

the tower support stands. For 

rack installation, attach the 

brackets to the UPS, install the 

rail kit in the rack if needed, and 

install the UPS in the rack.

NOTE: 

This UPS is not for use in a 

computer room as defined in the 

standard for the protection of 

electronic computer/data 

processing equipment of ANSI/

NFPA 75.

CONNECTIONS
4.  Connecting External 

Battery Cabinet 

(Optional)

External battery cabinets (EBC)

provide longer battery run-time 

for connected devices. Refer to 

GXT5 User Guide, to select the 

appropriate model and quantity 

for your GXT5 model and 

applications. 

•  Verify that the EBC breaker 

is in the “Off” position.

•  Connect one end of the 

supplied EBC cable to the 

UPS battery connector and 

autodetect port (terminal 

block 3) and one end to the 

EBC’s battery connector and 

autodetect port. If connecting 

more than one EBC, connect 

one end of the external 

battery cable to the second 

set of connectors on the 

battery cabinet, then connect 

the other end to the next 

battery cabinet.

EBC terminal

GXT5

TM

 UPS to External Battery Cabinet Connections 

GXT5‑8000/10KHVRT5UXLN

Shown

Single/First EBC

WIRING

Recommended external over-current protection

60 A (8 kVA)  

70 A (10 kVA)

Recommended wire size for all wires (75 °C copper 

wire)

6 AWG (16 mm

2

)

Maximum wire accepted by terminal block

6 AWG (16 mm

2

)

Terminal-block torque

20 in-lb (2.26 Nm)

Second EBC

Summary of Contents for Liebert GXT5-10KHVRT5UXLN

Page 1: ...l at microups warranty vertiv com 2 Choosing a location Install the UPS in a temperature controlled environment that is free of corrosive and conductive contaminants Avoid locations near heat or water sources and exposed to direct sunlight REAR PANEL OF GXT5 8000 10KHVRT5UXLN GXT5 UPS Description 1 Liebert IntelliSlot Port 2 Terminal block Dry contact communication connectors 3 RS 485 port 4 USB p...

Page 2: ...nal External battery cabinets EBC provide longer battery run time for connected devices Refer to GXT5 User Guide to select the appropriate model and quantity for your GXT5 model and applications Verify that the EBC breaker is in the Off position Connect one end of the supplied EBC cable to the UPS battery connector and autodetect port terminal block 3 and one end to the EBC s battery connector and...

Page 3: ... Ensure that the REPO connector on the rear of the unit has a jumper between pins 1 2 or that it is properly wired to an Emergency Power Off circuit normally closed 3 Make sure the breaker supplying power to the UPS is closed and close the input breaker and bypass breaker on the rear of the UPS 4 If necessary use the LCD display or a connected computer to adjust any required settings Refer to the ...

Page 4: ...d logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness herein Vertiv Group Corp assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions Specifications are subject to change without notice 4 SL 70529_REV...

Reviews: