Vertiv
| Liebert
®
ITA2
™
User Manual |
44
Outlet
Turn outlet On
—
Appears only when
outlet off
Turn outlet Off
—
Appears only when
outlet on
Reboot outlet
—
Appear sonly when
outlet on
Turn Off when UPS overload on
battery
YES, NO
NO
Turn off when UPS on battery for
0~4320 (min)
2
Turn Off when backup time less
than
0~4320 (min)
0
Turn Off when battery capacity
less than
20~80%
30%
Turn on when power returns for
0~4320 (min)
0
Monit
or
Language
English, Chinese, Spanish, French
English
Date
YYYY-MM-DD 2016-10-01
Time
HH:MM:SS
00:00:00
Display orientation
Auto-Rotate, Horizontal, Vertical
Auto-rotate
Audible alarm
Enable, Disable
Enable
Control port protocol
Modbus, Sensor
Sensor
Modbus address
1 ~ 128
1
IPv4 address
ddd.ddd.ddd.ddd ( 'd' is a decimal number)
—
Subnet mask
—
Gateway address
—
Change settings password
The six-digit numeric password can be any
numeral 0 to 9.
111111
Table 9
LCD parameter settings
(continued)
Menu
Item
Setting Range
Default Setting