2.6.2 Single-Input Configuration
1.
Remove the conduit box cover to gain access to the input and output terminal blocks.
2.
Remove the knockout plates and attach the conduits to the rear of the conduit box.
Hardwire Connections—UPS Input
3.
Leave the shorting busbars in place on the UPS input terminal block.
4.
, make these connections:
• Phase A cable from the upstream feeder panel to UPS Jumper 11
• Phase B cable from the upstream feeder panel to UPS Jumper 12
• Phase C from the upstream feeder panel to UPS Terminal 13
• Neutral from the upstream feeder panel to UPS Terminal 14 or 15
• The safety equipment ground cable from upstream feeder panel to UPS ground stud 10
WARNING
Risk of electrical shock. Can cause equipment damage, injury and death.
Before beginning installation, verify that all external overcurrent protection devices are
open (Off), and that they are locked out and tagged appropriately to prevent activation
during the installation.