Figure 51 Initial startup guidance, Pg. 5
4.2
Transfer Between Operation Modes
4.2.1 Transfer from Inverter Mode to Bypass Mode
To transfer to the internal bypass or turn Off the UPS when the UPS is operating in Normal Mode
(the inverter is supplying clean and protected power to the connected equipment):
1.
Press and hold the Power button for 2 seconds. If the bypass power is within normal operating range the
screen shown at the top left in
will appear, permitting transfer
To The Bypass
or
Turn Off UPS
.
2.
Use the Up/Down arrow keys to change or make a selection.
3.
Press the Enter key to confirm the action.
4.
Press the Enter key again.
If the bypass power is outside normal operating range, the screen shown in
where the only selection is to
Turn Off UPS
and confirm the action and press the Enter key.
Figure 52 Bypass normal interface