Figure 53 Bypass abnormal interface
4.2.2 Transfer From Bypass Mode to Inverter Mode
To transfer to the inverter (normal operation) or turn Off the UPS when the UPS is on internal
bypass mode:
1.
Press and hold the power button for 2 seconds. The screens shown in
will appear with the
choice of
Turn On UPS
or
Turn Off UPS
.
2.
Use the Up/Down arrow keys to change or make the selection.
3.
Press the Enter key.
4.
Confirm the action and press the Enter key.
If the UPS is operating in Eco Mode, the screen shown in
ll appear with the only choice is
Turn
Off UPS
. To do so, confirm the action and press the Enter key.
Figure 54 Transfer to Inverter Mode from Bypass Mode
NOTE
In Bypass mode, the load is powered directly by utility power.