57
7.1.1
Standard Battery Cabinet Backup Time with a Single UPS
.
NOTE
Run times shown in
are approximate. They are based on new, fully charged
batteries at a temperature of 77°F (25°C) with 100% resistive UPS loading. Different loading will
change the actual run times. Run times listed may vary by ±5% due to manufacturing variances of
the batteries.
Table 13
Backup time in minutes—8kVA/7.2kW
Number
Of
Battery
Strings
Load Level
100%
90%
80%
75%
70%
60%
50%
40%
30%
25%
20%
10%
7.2k
W
6.48k
W
5.76k
W
5.4k
W
5.04k
W
4.32k
W
3.6k
W
2.88k
W
2.16k
W
1.8k
W
1.44k
W
0.72k
W
1
13
15
18
19
21
26
33
40
56
75
101
166
2
33
36
40
45
49
61
76
102
135
151
167
345
3
52
61
71
77
82
103
126
147
167
211
330
650
4
76
91
103
109
121
137
152
181
227
323
480
880
5
103
112
130
137
143
156
181
219
328
347
600
1020
Table 14
Backup time in minutes—10kVA/10kW
Number
Of Battery
Strings
Load Level
100%
90%
80%
75%
70%
60%
50%
40%
30%
25%
20%
10%
10kW
9kW
8kW
7.5kW
7kW
6kW
5kW
4kW
3kW
2.5kW
2kW
1kW
1
8
9
11
12
13
17
22
29
43
54
72
150
2
22
25
29
33
36
43
55
74
102
124
157
318
3
38
43
50
54
59
74
89
116
159
193
240
497
4
54
62
74
80
85
103
125
160
214
262
330
676
5
74
83
94
103
111
132
160
202
274
335
422
868
Summary of Contents for Liebert ITA2-08KRT208
Page 1: ...Liebert ITA2 8 10kVA 60Hz 208 220V Three Phase UPS User Manual...
Page 40: ...Vertiv Liebert ITA2 User Manual 34 Figure 31 Status page menus...
Page 70: ...Vertiv Liebert ITA2 User Manual 64 NOTES...
Page 71: ...Vertiv Liebert ITA2 User Manual 65...
Page 72: ...Vertiv Liebert ITA2 User Manual 66...
Page 73: ......