Vertiv
| Liebert
®
ITA2
™
User Manual |
58
8.0
SPECIFICATIONS
Table 15
Specifications
Item Description
8kVA
10kVA
Input
3 Phase
4W+Gnd
Rated Voltage
208/220VAC, 3 Phase, 4W+Gnd
Voltage Range, VAC
96 ~ 144
Rated Frequency Hz
60
60
Frequency Range, Hz
40 ~ 70
Power Factor
≥0.99, at full load; ≥0.98, at half load
Output
3 Phase
4W+Gnd
Rated Power
8 kVA/7.2kW
10kVA/10kW
Voltage
208/220VAC (3 Phase 4W+Gnd)
Frequency Synchronization Range
Rated frequency ±3Hz. Configurable range: ±0.5Hz ~ ±5Hz
Frequency Track Rate
0.5Hz/s. Configurable Range: 0.2/0.5/1Hz/s (Single UPS),
0.2Hz/s (Parallel System)
Rated Power Factor
0.9
1
Crest Factor
3:1
3:1
Voltage Harmonic Distortion
< 4% (linear load); < 5% (non-linear load)
Dynamic Response Recovery Time,
ms
60
60
Overload Capacity
At 25°C: 105% ~ 125%, 5min; 125% ~ 150%, 1min; 150%, 200ms
Bypass Voltage
Upper Limit: +10%
Lower Limit: -10%, -15%, -20%; default -10%
AC-AC Efficiency
Up to 93.4%
Battery
Type
Sealed, Lead-Acid, Maintenance-Free
Number of Cells
192 by Default
Rated Voltage, VDC
384
Charge Current, Maximum, A
1.8
3.5
Transfer Time
Utility to Battery, ms
0
0
Inverter to Bypass
Synchronous Transfer: 0ms
Asynchronous Transfer (default): ≤20ms
(40ms, 60ms, 80ms, 100ms and 200ms are available)
Noise, db
<55
<55
Panel Display Mode
Color LCD
Safety
IEC/EN62040-1; UL/CSA
cULus (UL 1778 5th Edition, CSA No.22.2 107.3)
EMC
Conduction Emission
IEC/EN62040-2; FCC Part 15, Class A
Harmonic Current
IEC/EN61000-3-12
Surge Protection
IEC/EN-61000-4-5, Endurance Level 4 (4kV) (live line to earth),
Level 3 (2kV) (during live lines); ANSI C62.41, 6kV/2Ohms
Protection Level
IP20
IP20
Ambient
Condition
Operating Temperature
32 ~ 122°F (0 ~ 50°C) (0.7 will be derated above 122°F [50°C])
Storage Temperature
No Battery: -40 ~ 158°F (-40 ~ +70°C); With Battery: -13 ~ 131°F (-25 ~
+55°C)
Relative Humidity
5% RH ~ 95% RH, non-condensing
Altitude, ft. (m)
Sea Level to 10,000 (3000) without derating
Dimensions,
W x D x H, in.
(mm)
Net
16.9 x 19.7 x 5.1 (430 x 500 x 130)
Shipping
33.1 x 13.8 x 25.3 (842 x 350 x 642)
Summary of Contents for Liebert ITA2-08KRT208
Page 1: ...Liebert ITA2 8 10kVA 60Hz 208 220V Three Phase UPS User Manual...
Page 40: ...Vertiv Liebert ITA2 User Manual 34 Figure 31 Status page menus...
Page 70: ...Vertiv Liebert ITA2 User Manual 64 NOTES...
Page 71: ...Vertiv Liebert ITA2 User Manual 65...
Page 72: ...Vertiv Liebert ITA2 User Manual 66...
Page 73: ......