2.2.5 Features Available for EconoPhase or EEV Systems
Liebert® DSE and PDX-EEV Unheated Receiver
Liebert® DSE and Liebert® PDX with EEV systems require unheated receivers to manage refrigerant volume fluctuations in
the evaporator coil, which occur during normal operation. The receivers are field mounted on the Liebert® MC condenser
and are field piped in the liquid line between the condenser and the indoor unit. The receiver discharge must be mounted
higher than the EEV height of the indoor unit.