Condenser with Receiver
•
Cannot be installed below the evaporator.
•
EEV units: The outlet of the receiver on the outdoor MC condenser must be higher than the elevation of the
electronic expansion valves (EEV) inside the indoor unit. The vertical height of the receiver outlet must not
exceed 60 ft. (18.3 m) above the EEV.
•
TXV units: The bottom of the receiver on the outdoor MC condenser must be higher than the elevation of the
thermal expansion valves (TXV) inside the indoor unit. The vertical height of the bottom of the receiver must
not exceed 60 ft. (18.3 m) above the TXV.
•
Consult factory before installing units, condensers, and receivers outside these parameters.
•
Refer to DPN003954, DPN003993, and DPN003994 included in
Condenser without Receiver
•
The bottom of the condenser coil must be less than 15 ft. below the location of the TXV inside the indoor unit.
•
The vertical height of the bottom of the condenser coil must not exceed 60 ft. (18.3 m) above the TXV inside
the indoor unit.
•
Consult factory before installing units and condensers outside these parameters.
•
Refer to DPN003954 included in
NOTE: Failure to use compressor oils recommended by compressor manufacturer will void compressor warranty.
Consult Vertiv Technical Support or the compressor manufacturer for further recommendations or if you have
questions about compressor oils.
Refer to ASHRAE Refrigeration Handbook for general, good practice refrigeration piping. The indoor cooling unit has a
factory installed high pressure safety switch in the high side refrigerant circuit. A pressure relief valve is provided with
Liebert®Lee-Temp receivers and field installation is required. A fusible plug is installed in each Liebert® DSE receiver and
Liebert® PDX-EEV receiver. An optional fusible plug kit is available for field installation on condensers without receivers.
NOTE: Liebert® DSE systems require all indoor and outdoor field refrigerant piping to be insulated 1/2 in. minimum.
All outdoor insulation must be UV and ozone resistant.
•
Refer to Table 5.3 below, for recommended refrigerant piping sizes based on equivalent pipe lengths.
•
Refer to
Refrigerant Charge Requirements
on page 29, for the refrigerant charge requirements of the system.
5.1.2 Recommended Refrigerant Line Sizes
Indoor
Unit
Model
Equivalent Length, ft. (m)
50 (15)
100 (30)
150 (45)
300 (91)
450 (137)
Line sizes, OD Cu, in.
CR019RA/
CR020RA
Hot Gas Line
3/4
3/4
3/4
7/8
1
—
Liquid Line
5/8
5/8
5/8
3/4
—
CR035RA
Hot Gas Line
7/8
7/8
7/8
1-1/8
1
—
Liquid Line
3/4
3/4
3/4
7/8
—
Table 5.3 Recommended Refrigerant Line Sizes for R-410A with Standard and Digital Scroll Compressors
5 Piping
27
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...