Line Size O.D., in.
R-407C
R-410A
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
3/8
—
3.6 (1.6)
—
3.2 (1.4)
1/2
0.5 (0.2)
6.7 (3.0)
0.7 (0.3)
5.9 (2.7)
5/8
0.8 (0.4)
10.8 (4.8)
1.1 (0.5)
9.6 (4.3)
3/4
1.2 (0.5)
16.1 (7.2)
1.6 (0.7)
14.3 (6.4)
7/8
1.7 (0.8)
22.3 (10.0)
2.3 (1.0)
19.8 (8.8)
1-1/8
2.9 (1.3)
38.0 (17.0)
3.9 (1.7)
33.8 (15.1)
1-3/8
4.4 (2.0)
57.9 (25.9)
5.9 (2.6)
51.5 (23.0)
1-5/8
6.2 (2.8)
—
8.4 (3.7)
—
Data based on 50°F Evap, 15°F superheat, 125°F SCT, 10°F sub-cooling
Source: DPN002411, Rev. 8
Table 5.7 Interconnecting Piping Refrigerant Charge, lb/100 ft.
(kg/30m)
5.1.4 System Refrigerant Pressures
Maximum Design Operating Pressure (High Side)
R-407C
R-401A
Noted on the unit serial tag.
364 psig
2510 kPa
530 psig
3655 kPa
Table 5.8 System Refrigerant Pressures
5.1.5 Additional Oil Requirements
Refer to the indoor unit's installer/user guide to determine if additional oil is required for each circuit. The need for
additional oil is affected by compressor type, piping lengths, receiver, and total refrigerant charge.
5.2 Equipment Application Guidelines
Pump down must be disabled on the indoor unit when using the Liebert® MC condenser, due to the reduced volume in the
condenser coil.
We recommend adding a discharge line check valve and crankcase heater when connecting the MC condenser to Liebert®
indoor units built before 2012. The check valve and crankcase heater are needed for compressor protection. Additional
liquid line Schrader ports are required at the indoor unit to properly charge systems with MC condensers.
5.3 System Dehydration/Leak Test
Refer to the indoor unit's installer/user guide for the leak check and evacuation procedures for the entire thermal
management system. Refer to the section regarding the winter control system used on the condenser.
5.4 Charging for Condensers with Liebert® Lee-Temp Receivers
Consult the indoor unit’s installer/user guide for charging systems with Liebert® Lee-Temp receivers. These procedures are
identical to systems with fin/tube condenser coils, but the refrigerant volumes will be much lower.
5 Piping
31
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...