Model
Voltage
FLA
WSA
OPD
Small Platform
MCS028
208/230V
3.0
3.8
15
380V
1.4
1.8
15
460V
1.4
1.8
15
575V
1.2
1.5
15
MCS056
208/230V
6.0
6.8
15
380V
2.8
3.2
15
460V
2.8
3.2
15
575V
2.4
2.7
15
Medium Platform
MCM040
208/230V
2.3
2.9
15
380V
1.4
1.8
15
460V
1.4
1.8
15
575V
1.2
1.5
15
MCM080
208/230V
4.6
5.2
15
380V
2.8
3.2
15
460V
2.8
3.2
15
575V
2.4
2.7
15
MCM160
208/230V
9.2
9.8
15
380V
5.6
6.0
15
460V
5.6
6.0
15
575V
4.8
5.1
15
Table 6.2 Electrical Data, Three-Phase, 60Hz Condenser, Premium EC Fan Control
Vertiv | Liebert® MC Installer/User Guide
36
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...