Alarm ID
Meaning
Possible Cause
Handling Method
(1-4) 00
EC fan high link current
1. EC fan is locked.
2. EC fan is damaged.
For cause 1, check if EC Fan is locked..
For cause 2, replace EC Fan.
(1-4) 01
EC fan drive error
EC fan is damaged.
Replace EC Fan.
(1-4) 02
EC fan earth to ground fault
EC fan is damaged.
Replace EC Fan.
(1-4) 03
EC fan electronics heat sink
thermal overload
1. EC fan is locked.
2. EC fan is damaged.
3. Ambient temperature is too high.
For cause 1, check if EC fan is locked.
For cause 2, replace EC fan.
For cause 3, check ambient temperature.
(1-4) 04
EC fan hall failure
EC fan is damaged.
Replace EC fan.
(1-4) 05
EC fan IGBT failure
EC fan is damaged.
Replace EC fan.
(1-4) 06
EC fan line fault
Power supply abnormal
Check power supply
(1-4) 07
EC fan motor locked
Motor is locked.
Check if EC fan is locked.
(1-4) 08
EC fan motor thermal overload
1. EC fan is locked.
2. EC fan is damaged.
3. Ambient temperature is too high.
For cause 1, check if EC fan is locked.
For cause 2, replace EC fan.
For cause 3, check ambient temperature.
(1-4) 09
EC fan phase failure alarm
Phase failure
Check power supply.
(1-4) 10
EC fan specific uncategorized
alarm detected
Internal EC fan issue
Re-boot condenser if fans not running.
If alarm persists and fans not running, replace fan.
(1-4) 11
EC fan specific uncategorized
warning detected
(1-4) 12
EC fan electronics high
temperature condition.
1. EC Fan is locked.
2. EC Fan is damaged.
3. Ambient temperature is too high
For cause 1, check if EC fan is locked..
For cause 2, replace EC fan.
For cause 3, check ambient temperature.
(1-4) 13
EC fan high link voltage
1. EC fan input power supply high voltage
2. EC fan is damaged.
For cause 1, measure power supply voltage
and check if the voltage is normal.
For cause 2, replace EC fan.
(1-4) 14
EC fan low link voltage
1. EC Fan input power supply low voltage
2. EC Fan detection error
(1-4) 15
EC fan 485 communication failure
1. Communication between EC fan and
PCB board failure
2. EC fan 485 communication failure
3. Board has problems.
4. EC fan not receiving power
For cause 1, check EC fan communication circuit.
For cause 2, replace EC fan.
For cause 3, replace PCB board.
For cause 4, check fan model is not set for “0”,
check that the contactor for the particular fan is
energized, and check fan fuses.
Table 10.3 EC Fan Alarm Information
Vertiv | Liebert® MC Installer/User Guide
54
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...