11. Install the new cable glands included with the new EC fan. Torque for the cable glands is:
•
630 mm and 710 mm fans: 19.5 to 24.75 in-lb (2.2 to 2.8 Nm)
•
800 mm fans: 32.75 to 38 in-lb (3.7 to 4.3Nm)
Dispose of the old cable glands once the new glands are installed.
12. Add a compression nut to the wire—Do not tighten the nut.
13. Reconnect the wiring to the proper terminals and verify that the run jumper is in place. See Figure 11.1 on
page 59, and Figure 11.2 on page 60, for wiring details.
The torque for the electrical terminals is 11.5 in-lb (1.3 Nm). Tighten the compression nut to a torque of 22 in-lb
(2.5 Nm).
14. With the PCB powered, the board display should read
F00
. Refer to Figure 10.1 on page 46 and Figure 10.2
15. Press the ESC button.
16. Press the UP arrow button once:
•
If
P- -
is displayed, perform step 17.
•
if
P- -
is not displayed, perform steps 18 through 46.
17. If
P- -
is displayed, press the ENT button to enter the P- - Menu.
The P- - Menu allows compact setup/preparation of the condenser in the factory or in the field. Use the
functions described in Table 11.1 below, to establish a default control configuration for the board.
NOTE: The complete list of P--, C--, and F-- parameters is located inside the lid of the electrical box panel.
Item
ID
Meaning
Default
Notes
P01
Enter
Preparation
Mode
0
Setting this value to ‘1’ enables preparation mode. All other P—menu items are disabled until this value is 1. Note that
control operations may be affected during preparation mode, therefore the cooling unit should be off. Setting this
value back to 0 creates new default values based upon selections in this menu. After default values are established,
the board exits preparation mode and reboots.
P02
Automatic
VSD
Configuration
1
This item should only be used to address the VSDs for the unit. The value entered indicates the model of the VSD:
1 – EBM
2 – Ziehl-Abegg
3 – Fans Tech
All fans must be the same model to use this parameter. When
ENT
is pressed, the board will operate and power
contactors for the VSDs and assign ModBus addresses. This procedure may take up to five minutes to complete.
P03
Refrigerant
Type
2
1 = R22
2 = R407C
3 = R410A
P04
Number
of Circuits
1
1 = Single Circuit
2 = Dual Circuit
Table 11.1 P-- Menu Items and Definitions
Vertiv | Liebert® MC Installer/User Guide
62
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...