6.3 Wye vs. Delta Connected Power Supply
Acceptable Power Supplies—208 V to 575 V Nominal Units
•
208 V Wye with solidly-grounded neutral and 120 V line to ground
•
380 V Wye with solidly-grounded neutral and 220 V line to ground
•
480 V Wye with solidly-grounded neutral and 277 V line to ground
•
575 V Wye with solidly-grounded neutral and 322 V line to ground (uses step down transformers)
•
Wye with high resistance (or impedance) ground
•
Delta with corner ground
Unacceptable Power Supplies
•
Delta without ground or with floating ground
•
Delta with grounded center tap
6.4 Low Voltage Control Wiring—CANbus Communication
NOTICE
Risk of control malfunction. Can cause improper unit operation.
Verify that all low voltage electrical wiring has been performed per the schematic diagram provided and that
all low voltage wiring connections are tight.
CANbus communication and interlock wiring are required between the indoor and the outdoor units. CANbus cables are
supplied by others to connect the indoor unit to the outdoor condenser. No special considerations are required when the
total external cable connection between the indoor unit and outdoor unit is less than 450 ft. (137 m). A CANbus isolator is
required for total external cable connections longer than 450 ft. (137 m) but less than 800 ft. (243 m).
The control wiring connections are described in the submittal documents included in the
The following tables list the relevant documents by number and title.
Document Number
Title
DPN003267
CANbus and Interlock Connections between Liebert® DS and Liebert® MC Condenser (Premium)
DPN003266
CANbus and Interlock Connections between PDX Unit and Liebert® MC Condenser (Premium)
DPN002841
CANbus and Interlock Connections between 600mm (24in) and Liebert® MC (Premium)
DPN003036
CANbus and Interlocking Connections between Liebert® PDX Unit and Liebert® MC Condenser (Premium)
DPN003284
CANbus and Interlock Connections Using 1 Liebert® MC Condenser and Optional EconoPhase Unit
DPN002361
CANbus and Interlock Connections Using 2 Liebert® MC Condensers and Optional EconoPhase Unit
Table 6.4 CANbus Communication Connection Drawings
Vertiv | Liebert® MC Installer/User Guide
38
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...