Figure 10.7 History Alarms Menu
Item
Description
1
Pressing ENT displays the history alarm item(s), which alternately displays the sequence number and the alarm ID.
2
Pressing up arrow, cycles up through the sequence numbers.
3
Pressing down arrow, cycles down through the sequence numbers.
4
Pressing ESC returns to the history alarms menu.
Alarm ID
Meaning
Possible Cause
Handling Method
000
CAN communication failure
Communication circuit missing or
damaged.
Check communication circuit. Ignore alarm
on condensers without CAN connections.
001
Ethernet communication failure
Ethernet hardware or connection failure
Ignore alarm, Ethernet connection is not
present.
002
USB communication failure
USB device or file is damaged.
Replace USB device or file.
003
Data corruption
Memory chip is damaged.
Replace PCB board.
004
System error
Internal error
Reboot. If reboot fails, consult factory.
Table 10.2 System Alarm Information
Vertiv | Liebert® MC Installer/User Guide
52
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...