33. Press the ENT button.
34. Use the UP or DOWN arrow button to the correct fan address number. Fan 1 should be 1 (fan closest to electric
panel end). Fan 2 should be 2, etc.
35. Press the ENT button. The display flashes "
888
" when the command is accepted.
36. Press the ESC button for the parameter to be shown on the display.
37. Repeat steps 30 through 36 for the rest of the fans that need to be addressed.
38. After the last fan is addressed, unplug the power plug, P24, from the control board, and wait 30 seconds.
39. Plug all the contactor output plugs back into the board in their correct positions.
40. Plug P24 back into the control board.
41. After the control board completes its boot cycle and all the contactors are energized, wait five seconds.
42. Press the ESC button.
43. Use the UP or DOWN arrow button until
A--
is on the display.
44. Press ENT button.
45. Use the UP or DOWN arrow button to see if any of the following errors are shown.
115: Unable to communicate with Fan 1.
215: Unable to communicate with Fan 2.
315: Unable to communicate with Fan 3.
415: Unable to communicate with Fan 4.
•
If any of these errors appear, check the communication wiring at the problem fan and the fan before it.
•
If the wiring is correct and properly wired to the terminal, repeat the fan addressing procedure in steps
30 through 36.
46. If none of the errors listed in step 45 displays, press the ESC button.
11.3.1 Verifying the Fan Address
To verify that each fan has a unique address:
1.
Use the UP or DOWN arrow button until
C--
displays.
2.
Press the ENT button.
3.
In the Manual/System Control Selection parameter use the UP or DOWN arrow button until
C24
displays.
4. In the Manual Control configuration parameter, press the ENT button.
5.
Use the UP or DOWN arrow button to select
0
.
6. Press the ENT button.
The display reads "
888
" if the command is accepted.
7.
Press the ESC button to display
C24
.
8.
Use the UP or DOWN arrow button until
C34
displays.
9. Press ENT button.
If Fan 1 is running, the fans speed should display in terms of percentage of full speed. If Fan 1 is not running,
0.00
should display.
10. Use the UP or DOWN arrow button to enter
100%
speed.
Vertiv | Liebert® MC Installer/User Guide
64
Summary of Contents for Liebert MC series
Page 1: ...Liebert MC Installer User Guide 60 Hz Air Cooled Microchannel Condenser Premium EC Fan ...
Page 8: ...Vertiv Liebert MC Installer User Guide 4 This page intentionally left blank ...
Page 14: ...Vertiv Liebert MC Installer User Guide 10 This page intentionally left blank ...
Page 28: ...Vertiv Liebert MC Installer User Guide 24 This page intentionally left blank ...
Page 44: ...Vertiv Liebert MC Installer User Guide 40 This page intentionally left blank ...
Page 46: ...Vertiv Liebert MC Installer User Guide 42 This page intentionally left blank ...
Page 48: ...Vertiv Liebert MC Installer User Guide 44 This page intentionally left blank ...
Page 76: ...Vertiv Liebert MC Installer User Guide 72 This page intentionally left blank ...
Page 88: ...Vertiv Liebert MC Installer User Guide 84 This page intentionally left blank ...
Page 90: ...Vertiv Liebert MC Installer User Guide 86 This page intentionally left blank ...