User Manual 10H52246UM60 - Rev. 1 - 01/2017
ECLECTRICAL INSTALLATION
Connecting the system input
1. 3-in 3-out, common input configuration (factory default)
Refer to Figure 3-5, connect the AC input cables to the bypass input terminals (bA-bB-bC) in the cabinet, and
ensure that the three copper shorting bars are connected between the rectifier input terminals (mA-mB-mC) and
the corresponding bypass input terminals. Connect the input neutral line to the neutral terminal N in the cabinet.
Ensure correct phase rotation.
Note that the common input copper shorting bars are factory fitted.
+
mA mB mC
N
oN
oA oB oC
N
-
PE
Mains input
Output
Shorting copper bar of
common input configuration
Figure 3-5
3-in 3-out, common input configuration cable connection (factory default)