SPECIFICATION
User Manual 10H52246UM60 - Rev. 1 - 01/2017
83
Chapter 11
Specifications
This chapter lists the UPS specifications.
11.1
Conformance And Standards
The UPS has been designed to comply with the European and international standards listed in Table 11-1.
Table 11-1
European and international standards
Item
Normative reference
General safety requirements for UPS
IEC/EN 62040-1+A1:2013/AS62040-1
EMC requirements for UPS *
IEC/EN 62040-2:2006/AS62040-2
Method of specifying the performance and test requirements of UPS
IEC/EN 62040-3/AS62040-3 (VFI SS 111)
The product standards in this table incorporate the relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series
and 60529).
* Category C3 (C2 optional)
11.2
Environmental Specifications
Table 11-2
Environmental characteristics
Item
Unit
Rated power (kVA)
60kVA
Noise at 1m (at front)
dB (A)
60
Altitude
m
≤ 1000 (derate power by 1% for every 100m above 1000m)
Relative humidity
%RH
0 ~ 95%, non condensing
Operating temperature
°C
0 ~ 40°C (Note: Battery life is halved for every 10°C increase above 20°C)
Storage and shipping temperature
for UPS
°C
-40°C ~ +70°C
Over-voltage level
Overvoltage level 2
Pollution level
Pollution level 2
11.3
Mechanical Specifications
Table 11-3
Mechanical specifications
Item
Unit
Rated power (kVA)
60kVA
Dimensions (W × D × H)
mm
600 × 850 × 1600
Net weight
kg
223.5
Gross weight
kg
258.5
Color
Black
ZP7021
Protection degree, IEC (60529)
IP20 (front door open or closed)
11.4
Electrical Specifications (Rectifier Input)
Table 11-4
Rectifier AC input (mains)
Item
Unit
Rated power (kVA)
60kVA
Rated AC input voltage
1
Vac
380/400/415, 3-phase 4-wire (+PE) TN/TT power distribution system
Input voltage range
2
Vac
305 ~ 477
Frequency
2
Hz
50/60 (range: 40 ~ 70)
Power factor
kW/kVA, full load
(half load)
0.99 (0.98)
Input current
A, rated
3
84
Total current harmonic
distortion
%
Linear full load < 3% (battery float charge) (3-in 3-out)
Non-linear full load < 5% (battery boost charge) (3-in 3-out)
Duration of progressive
power walk-in
s
5s to reach full rated current (selectable 10s through 25s in 5-second
intervals)
1. Rectifiers operate at any of the rated voltages without further adjustment.
2. At 305V the UPS maintains the specified output voltage at rated load without discharging the battery.
3. IEC/EN 62040-3/EN50091-3: at nominal load and input voltage 400V, battery fully charged.