81
Application of INTELLI SLOT
Figure 5-9 BACnet Protocol Settings
5.3.6. Configure BACnet IP Protocol
Contact the system administrator or building management system administrator if any ambiguity is faced
about the settings.
1. Select Unity Tab > Protocols > BACnet IP.
2. Click on Edit and enter a User name and password if required.
3. Set the BACnetIP/Port Number
4. If the Liebert IntelliSlot Unity card is on a different subnet, a possibility when the monitored units are part of a
Liebert SiteScan network or other third-party monitoring service:
• Choose whether to enable Register as Foreign Device.
• Enter the IP address of the BBMD (BACnet Broadcast Management Device).
• Enter a time in seconds for Foreign Device Time-to-Live.