3.4 Audible-tone Indicators

TYPE

INDICATES                                                

1 beep every 10 seconds

Battery mode

2 beeps every second

UPS warning

2 beeps every 5 seconds

Low-battery warning

3 beeps every 30 seconds

Replace-battery warning

Constant, solid tone

UPS fault

3-second tone followed by 2 beeps

Power-on in battery self-test mode

1 long tone

Power off

3 beeps

Manual battery self-test

Table 3.3 Tones and Beeps of the UPS

3.5 Warnings

The UPS has three early-warning indicators that allow the UPS to function normally for a short period
before the outputs are shut-off.

ICON
DISPLAYED

AUDIBLE TONE

DESCRIPTION

SUGGESTED TROUBLESHOOTING

1 beep every second

Output-overload. The load devices
plugged-in to the UPS output are drawing
more power than the UPS rating.

Reduce the load to below the UPS rating in the specifications
table, see

Specifications

on page 19.

Constant, solid tone

Site-wiring fault. Problem detected with the
outlet wiring to which the AC input of the
UPS is connected.

Power-off the UPS and contact an electrician to correct the
wiring. Possible causes are line and neutral are reversed or
there is no ground conductor.

3 beeps every 30
seconds

The battery is weak or damaged.

Charge the UPS battery for at least 12 hours, or replace the
battery, see

Battery Replacement

on page 18.

Table 3.4 Warning Indicators and Actions

3.6 Faults

The UPS displays fault codes when it detects a problem and automatically shuts-off output power.

FAULT
CODE

DESCRIPTION

SUGGESTED TROUBLESHOOTING

E01

Output short circuit.

Turn-off the UPS, disconnect all loads, and restart the UPS.

If the fault is still active, contact Vertiv technical support for a replacement.

If the fault is no longer active, plug in equipment one at a time to locate the device
with the short circuit.

E02

Output overload exceeded warning
time, and output is shut off.

Turn-off the UPS, disconnect all loads, and restart the UPS. Plug in equipment one at a time and
make sure not to exceed the UPS rating for load capacity.

E03

Un-used.

Un-used.

E04

Internal inverter circuitry failure
during start-up self-test.

Turn-off the UPS and call Vertiv technical support for a replacement unit.

E05

Battery-charge failure.

Turn-off the UPS and call Vertiv technical support for a replacement unit.

E06

Internal battery is dead or damaged.

Charge the UPS for at least 12 hours or replace the battery, see

Battery Replacement

on page

18.

Table 3.5 Fault Codes and Actions

Vertiv

| Liebert® PSA5™ Installer/User Guide |

14

Summary of Contents for Liebert PSA5

Page 1: ...Liebert PSA5 Installer User Guide...

Page 2: ...any installation or operational issues with your product check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures For additional assistance visi...

Page 3: ...ging Ports 10 2 4 5 Connecting AC Input 10 3 Operation 11 3 1 Modes of Operation 11 3 1 1 Off Mode 11 3 1 2 On Normal Mode 11 3 1 3 On Automatic Voltage Regulation AVR Mode 11 3 1 4 On Battery Mode 11...

Page 4: ...Vertiv Liebert PSA5 Installer User Guide 4...

Page 5: ...ed during the installation and maintenance of the UPS and batteries Read this manual thoroughly and the safety and regulatory information available at https www vertivco com ComplianceRegulatoryInfo b...

Page 6: ...Vertiv Liebert PSA5 Installer User Guide 6 This page intentionally left blank...

Page 7: ...t PSA5 provides the run time to save work in process With the Liebert MultiLink shutdown software you can receive remote alerts and have unattended orderly shutdown of your systems 1 1 Available Model...

Page 8: ...y 5 USB charging ports 5 V 2 1 A max combined 6 Surge protected only receptacles 7 Battery backed and surge protected receptacles 8 USB communication port Type B 9 RJ11 45 connectors for phone fax mod...

Page 9: ...tions Place it in an area of unrestricted air flow around the unit away from water flammable liquids gases corrosives and conductive contaminants Avoid direct sunlight The socket outlet should be near...

Page 10: ...tion of the UPS To use this feature plug the provided USB cable into USB Type B port located on the rear panel of the UPS and the other end into an open USB port on your computer 2 4 4 USB Charging Po...

Page 11: ...cts the low voltage and allows the battery backed up outlets to be on with the normal expected voltage The internal batteries are charging NOTE The surge only outlets will have the abnormally low inpu...

Page 12: ...Self test mode Press quickly to wake the display 2 Silence Battery mode Alarm button Press and hold for 2 seconds during On Battery mode to mute the battery alarm beep Press quickly to wake the displ...

Page 13: ...ng See Warnings on page 14 for more details 5 Site wiring fault warning when lit See Warnings on page 14 for more details 6 Output load level graph in 25 increments 7 Numeric display of UPS operationa...

Page 14: ...s every 30 seconds The battery is weak or damaged Charge the UPS battery for at least 12 hours or replace the battery see Battery Replacement on page 18 Table 3 4 Warning Indicators and Actions 3 6 Fa...

Page 15: ...3 8 Normal Shut down 1 Press and hold the power button for 1 second The outlets are turned off 2 Disconnect AC input power 3 Remove the battery cover and disconnect the battery connector 3 9 Full Shu...

Page 16: ...Vertiv Liebert PSA5 Installer User Guide 16 This page intentionally left blank...

Page 17: ...ny objects into the ventilation holes or other openings of the UPS Do not place the UPS power cord where it might be damaged 4 2 Battery Charging The batteries are valve regulated non spill able lead...

Page 18: ...lling the two pieces apart see Figure 4 1 below Figure 4 1 Removing cover and disconnecting battery 4 Slide out the existing battery and disconnect bottom top half of the connector cable from the two...

Page 19: ...asurement Tolerance 5 High Line Normal Mode to Battery Mode 143 VAC High Line Battery Mode to Normal Mode 138 VAC Low line AVR Mode to Normal Mode 110 VAC Low line Normal Mode to AVR Mode 105 VAC Low...

Page 20: ...Model Leoch DJW12 7 0 CSB GP1272 Leoch DJW12 9 0 CSB HR1234W or UPS12460 Vertiv PSA5 24VBATTKIT Leoch DJW12 9 0 CSB HR1234W or UPS12460 Battery Quantity x VDC x Ah 1 x 12V x 7 0 Ah 1 x 12V x 9 0Ah 2...

Page 21: ...3 40 14 10 10 15 50 8 8 7 11 60 7 5 5 8 70 5 4 5 4 6 75 4 2 3 2 3 6 4 5 80 4 3 3 5 4 90 3 2 5 2 5 3 5 100 2 2 2 3 Note Run times in this table are approximate They are based upon new fully charged sta...

Page 22: ...Vertiv Liebert PSA5 Installer User Guide 22 This page intentionally left blank...

Page 23: ...unter with your Liebert product Please call or e mail us Technical support e liebert upstech vertivco com p 1 800 222 5877 menu option 1 Monitoring support e liebert monitoring vertivco com p 1 800 22...

Page 24: ...Vertiv Liebert PSA5 Installer User Guide 24 This page intentionally left blank...

Page 25: ......

Page 26: ...logos referred to are trade names trademarks or registered trademarks of their respective owners While everyprecaution has been taken to ensure accuracyand completeness herein VertivCo assumes no resp...

Reviews: