5.1 Run-time Tables
MODEL RATING
LOAD PERCENT OF CAPACITY
500 VA/300 W
700 VA/420 W
1000 VA/600 W
1500 VA/900 W
10%
74
60
53
64
20%
33
27
22
37
25%
23
17
16
25
30%
21
15
14
23
40%
14
10
10
15
50%
8
8
7
11
60%
7
5
5
8
70%
5
4.5
4
6
75%
4.2
3.2
3.6
4.5
80%
4
3
3.5
4
90%
3
2.5
2.5
3.5
100%
2
2
2
3
Note: Run times in this table are approximate. They are based upon new, fully charged standard battery modules
at a temperature of 25 degC (77 degF) with 100% resistive UPS loading.
Table 5.2 PSA5-120 Battery Run Times