UPS
C
ONTROLS AND
C
ONNECTIONS
(
FOR
PSL
1500BX/2000BX)
10B
Figures 9
– Front Panel
Figure 11
– Rear Panel (IRAM 230V)
Figure 10
– Rear Panel (NEMA 120V)
Figures 12
– Rear Panel (IEC 230V)
UPS Status, Alarm Conditions and Alerts
Condition
LED
Color
Solid/Flashing
Audible Alarm
Normal mode
LED 1
Green
Solid
(none)
Load level in Normal mode
LED 2
– LED 5
*Indicating load level in %
Green
Solid
(none)
Overload in Normal mode
Green
Solid
Every 0.5 second
Battery mode
LED 1
Green
Flashes
Every 10 seconds
Battery level in Battery
mode
LED 2
– LED 5
*Indicating battery level in %
Green
Solid
Battery low in Battery mode
LED 1
Green
Flashes
UPS shuts down
immediately.
Fault
LED 6
Red
Solid
Continuously sounding
until UPS shuts down
LED 1 green
=Status LED)
LED 2- LED 5 ( green
= Load/battery status
indicators)
On/Off
button
LED 6 (red=fault)
Circuit breaker
Battery backup
outlets (8)
USB Port
(option)
RJ45 Network
Surge
Protection
(option)
AC input
Battery backup
outlets (4)
USB Port
(option)
RJ45 Network
Surge
Protection
(option)
AC input
Circuit breaker
USB Port
(option)
AC input
RJ45 Network
Surge
Protection
(option)
Battery backup