background image

3.2 Controls

Figure 3.1 Buttons on PST5-350MT120 AND PST5-500MT120 Models

ITEM

DESCRIPTION

1

Power button.

Press-and-hold for 1 second to cycle between on and off mode.

Press-and-hold for 3 seconds to enter battery self-test mode.

Table 3.1 Button Controls

Figure 3.2 Buttons on PST5-660MT120 AND PST5-850MT120 Models

ITEM

DESCRIPTION

1

Scroll button.

When the UPS is in On mode, press to cycle through UPS operating parameters.

Press-and-hold for 2 seconds during Battery mode to mute the battery-alarm beep.

Press quickly to wake the display.

2

Power button.

Press-and-hold for 1 second to cycle between On and Off mode.

Press-and-hold for 3 seconds to enter Battery Self-test mode.

Press quickly to wake the display.

Table 3.2 Button Controls

Vertiv

| Liebert® PST5™ Installer/User Guide |

14

Summary of Contents for Liebert PST5-850MT120

Page 1: ...Liebert PST5 Installer User Guide ...

Page 2: ...r any installation or operational issues with your product check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures For additional assistance visit https www VertivCo com en us support ...

Page 3: ... Communication Connection 12 2 4 5 USB Charging Ports 12 2 4 6 Connecting AC Input 12 3 Operation 13 3 1 Modes of Operation 13 3 1 1 Off Mode 13 3 1 2 On Normal Mode 13 3 1 3 On Battery Mode 13 3 1 4 Fault Mode 13 3 1 5 Battery Self test Mode 13 3 2 Controls 14 3 3 Display panel Indicators 15 3 4 Audible tone Indicators 17 3 5 Warnings 17 3 6 Faults 18 3 7 Normal Start up 18 3 8 Normal Shut down 1...

Page 4: ...Vertiv Liebert PST5 Installer User Guide 4 ...

Page 5: ...wed during the installation and maintenance of the UPS and batteries Read this manual thoroughly and the safety and regulatory information available at https www vertivco com ComplianceRegulatoryInfo before attempting to install connect to supply or operate this UPS Vertiv Liebert PST5 Installer User Guide 5 ...

Page 6: ...Vertiv Liebert PST5 Installer User Guide 6 This page intentionally left blank ...

Page 7: ...t PST5 provides the run time to save work in process With the Liebert MultiLink shutdown software you can receive remote alerts and have unattended orderly shutdown of your systems 1 1 Available Models MODEL NUMBER NOMINAL POWER RATING PST5 350MT120 PST5 350MT120TAA 350 VA 200 W PST5 500MT120 PST5 500MT120TAA 500 VA 300 W PST5 660MT120 PST5 660MT120TAA 660 VA 400 W PST5 850MT120 PST5 850MT120TAA 8...

Page 8: ... 2 Red Fault LED 3 Power button 4 Green Mode LED 5 Battery backed and surge protected output power receptacles 6 Input Power Cord 7 Input Circuit Breaker 8 RJ11 45 connectors for phone fax modem or network surge protection 9 USB Type B connector for USB communication with a PC for UPS monitoring and PC shut down Vertiv Liebert PST5 Installer User Guide 8 ...

Page 9: ... surge protected output power receptacles 6 Input Power Cord 7 Input Circuit Breaker 8 USB charging port 5 V 2 0 A 9 Coax Cable connections for cable modem DSS receiver or cable TV converter surge protection connection 10 RJ11 45 connectors for phone fax modem or network surge protection connection 11 USB Type B connector for USB communication with a PC for UPS monitoring and PC shut down Vertiv L...

Page 10: ...Vertiv Liebert PST5 Installer User Guide 10 This page intentionally left blank ...

Page 11: ...tions on page 21 Place it in an area of unrestricted air flow around the unit away from water flammable liquids gases corrosives and conductive contaminants Avoid direct sunlight The socket outlet should be nearby and easily accessible This UPS is not for use in a computer room as defined in the standard for the Protection of Electronic Computer Data Processing Equipment ANSI NFPA 75 NOTE Operatin...

Page 12: ... www VertivCo com Use of this feature is not required for proper operation of the UPS To use this feature plug the provided USB cable into USB Type B port located on the side panel of the UPS and the other end into an open USB port on your computer 2 4 5 USB Charging Ports NOTE For PST5 660MT120 and PST5 850MT120 models only The PST5 has an easily accessible side panel USB Type A charging port Thi...

Page 13: ...he internal batteries are charging 3 1 3 On Battery Mode The UPS input is not plugged in or the voltage source has become extremely low or high and unusable The UPS automatically switches to the internal battery to provide normal usable voltage to the battery backed up outlets NOTE The surge only outlets will not have power 3 1 4 Fault Mode An error or fault condition has occurred The battery back...

Page 14: ...0 AND PST5 850MT120 Models ITEM DESCRIPTION 1 Scroll button When the UPS is in On mode press to cycle through UPS operating parameters Press and hold for 2 seconds during Battery mode to mute the battery alarm beep Press quickly to wake the display 2 Power button Press and hold for 1 second to cycle between On and Off mode Press and hold for 3 seconds to enter Battery Self test mode Press quickly ...

Page 15: ...t Figure 3 3 LED indicators on PST5 350MT120 AND PST5 500MT120 Models ITEM DESCRIPTION 1 Warning Fault red LED See Warnings on page 17 and Faults on page 18 for descriptions and troubleshooting 2 On AC Battery green LED On solid when the UPS is in On Normal mode Blinking when the UPS is in On Battery mode Table 3 3 Front panel Indicators Vertiv Liebert PST5 Installer User Guide 15 ...

Page 16: ...overload warning when flashing See Warnings on page 17 for more details 5 Output load level graph in 25 increments 6 Numeric display of UPS operational parameters VAC input output voltage Hz input output frequency 7 Fault when lit Fault codes indicated E01 E04 E05 E06 See Faults on page 18 for more details 8 Battery capacity graph in 25 increments Table 3 4 Display Icons and Indicators Vertiv Lieb...

Page 17: ...to below the UPS rating in the specifications table see Specifications on page 21 Blinking 2 beeps every 5 seconds or 3 beeps every 30 seconds The battery is weak or damaged Charge the UPS battery for at least 12 hours or replace the battery see Battery Replacement on page 19 Table 3 6 Warning Indicators and Actions for PST5 350MT120 AND PST5 500MT120 Models ICON DISPLAYED AUDIBLE TONE DESCRIPTION...

Page 18: ...rn off the UPS disconnect all loads and restart the UPS If the fault is still active contact Vertiv technical support for a replacement If the fault is no longer active plug in equipment one at a time to locate the device that is causing the fault E05 Battery charge failure Turn off the UPS and call Vertiv technical support for a replacement unit E06 Internal battery is dead or damaged Charge the ...

Page 19: ...ously when it is connected to the utility input power If the PST5 will be stored for a long time we recommend connecting the UPS to input power for at least 24 hours every 4 to 6 months to ensure full recharge of the batteries 4 3 Battery Replacement IMPORTANT Before you proceed please review the battery safety precautions available at https www vertivco com ComplianceRegulatoryInfo You may safely...

Page 20: ...g the last wire to the battery there can be a small spark This is normal 7 Seat the battery fully into the UPS and replace the compartment cover and screw 8 Press and hold the power button for 3 seconds to initiate the battery self test and clear any previous battery fault warning 9 Properly dispose of the old batteries at an appropriate recycling facility or return them to Vertiv in the packing m...

Page 21: ...50 VAC 7 A 250 VAC 10 A 250 VAC Surge Energy Rating 316 Joules Input Cord 6 ft attached with NEMA 5 15P OutputAC OnUtility Nominal Voltage 120 VAC Voltage Range 90 145 VAC Frequency Range 60 Hz 5 Hz Efficiency 95 at full load OutputAC OnBattery Nominal Voltage 120 VAC Voltage Range Nominal 8 at onset 15 at EOD Frequency Range 60 Hz 1 Hz Waveform PWM Simulated Sine wave Transfer Time 6 8 ms typical...

Page 22: ...ture deg degC 32 104 0 40 Operating Elevation feet meter 0 9 842 0 3 000 Relative Humidity 0 95 non condensing Storage Temperature degF degC 5 to 113 15 to 45 Storage Elevation feet meter 0 49 212 0 15 000 Audible Noise 40 dBA 3 ft 1 m from all sides Agency Safety cTUVus UL 1778 5th Edition CSA 22 2 No 107 3 2014 RFI EMI FCC part 15 subpart B CLASS B Surge Immunity EN61000 4 5 Level 2 Line Neutral...

Page 23: ... 40 19 12 11 9 50 11 9 7 5 6 5 60 10 7 6 5 5 70 8 5 5 5 4 75 7 2 5 2 4 2 3 2 80 7 5 4 3 90 5 3 5 3 2 100 4 3 2 1 5 Note Run times in this table are approximate They are based upon new fully charged standard battery modules at a temperature of 25 degC 77 degF with 100 resistive UPS loading Table 5 2 PST5 120 Battery Run Times Vertiv Liebert PST5 Installer User Guide 23 ...

Page 24: ...Vertiv Liebert PST5 Installer User Guide 24 This page intentionally left blank ...

Page 25: ...ounter with your Liebert product Please call or e mail us Technical support e liebert upstech vertivco com p 1 800 222 5877 menu option 1 Monitoring support e liebert monitoring vertivco com p 1 800 222 5877 menu option 2 Warranty support e microups warranty vertivco com p 1 800 222 5877 menu option 3 Vertiv Liebert PST5 Installer User Guide 25 ...

Page 26: ...Vertiv Liebert PST5 Installer User Guide 26 This page intentionally left blank ...

Page 27: ......

Page 28: ... logos referred to are trade names trademarks or registered trademarks of their respective owners While everyprecaution has been taken to ensure accuracyand completeness herein VertivCo assumes no responsibility and disclaims allliability for damages resulting from use of this information or for any errors or omissions Specifications are subject to change without notice SL 70202_REV2_8 18 590 1788...

Reviews: