Chapter 3 Web Page Of RDU-A G2 29
RDU-A G2 Intelligent Monitoring Unit User Manual
Team parameters
Default
Low limit
Upper limit
Notes
Standard
version
Authorized
version
Return air humidity
40%
20%
60%
/
√
Deviation of return
air humidity
5%
1%
10%
/
√
AC polling count
1
1
Lower value between
the running AC
number and the
backup AC number
√
√
Frequency of AC
team polling
Daily
Daily, Weekly
/
√
√
Interval
1
1
99
Daily mode
√
√
On every
1
1
7
Weekly mode
Mon, Tue, Wed,
Thur, Fri, Sat, Sun
√
√
Start at
00:00
00:00
23:00
/
√
√
Team polling by
manual
No
No
Yes
Used for test
√
√
Reset AC status
No
No
Yes
Initializing AC status
√
√
AC Turn on
temperature
25
15
30
√
√
AC Turn off
temperature
17
15
30
√
√
Note:
√
means the corresponding version can be configured
Note
1. If you need the RDU-A G2 authorized version, please contact the Emerson customer service center and purchase it. The
contact telephone number is 4008876510.
2. Only four Emerson DME series ACs with standard configuration are supported by default.
3. RDU-A G2 supports at most eight teams.
2. AC Parameters
Click the
TeamWork Setting
submenu under the
AC TeamWork
menu, and then click the
AC Parameters
button,
the AC parameters setting page pops up, as shown in Figure 3-30.