34 Chapter 3 Web Page Of RDU-A G2
RDU-A G2 Intelligent Monitoring Unit User Manual
Power Consumption Mode
In Power Consumption Mode, the system will count the device power consumption valve within 8h every 8h from
00:00:00 to 00:00:00 on next day, and calculate an average valve of a day after three times of counting as the power
consumption PUE of that day. The counting mode is similar to that of power mode.
Note
1. On the day you perform Calculation Setting, the system will calculate the counting times and valves from the setting time to
00:00:00 on next day, and use them to calculate an average valve as the PUE of that day.
2. If
Power Mode
is selected, you need to select power signals; if
Power Consumption Mode
is selected, you need to select
power consumption signals.
2. System Load Percent Setting
You can configure the actual power and rated power to calculate the system load percent, and the rules are as
follows:
System load percent = actual power / rated power
Among the above, the actual power is summary of the three power signals on the right of
Actual Power
.
3.4.4 Alarm Management
The Alarm Management menu supplies alarm centralized management function, enabling you of self-defining alarm
notification and alarm linkage rules, and viewing historic alarm.
On the RDU-A G2 homepage, click the
Alarm Management
menu on the left, four submenus appear, including
Current Alarm
,
History Alarm
,
Alarm Notification
and
Alarm Actions
.
Current Alarm
Click
Current Alarm
submenu under the
Alarm Management
menu, or refer to
3.3.6 Real-Time Alarm Prompt
Setting
, the current alarm list will pop up, as shown in Figure 3-34.
Figure 3-34 Current alarm
1. You can click the tabs above the alarm list to view current alarms according to alarm levels.