Chapter 3 Web Page Of RDU-A G2 37
RDU-A G2 Intelligent Monitoring Unit User Manual
Figure 3-38 SMS/Email server configuration
On the page shown in Figure 3-38, you can perform
SMS Modem Configuration
and
RDU Voice Notification
System Setting
for alarm notification reminding through SMS or phone, you can also perform
Email Server
Configuration
for alarm notification reminding through email, the procedures are as follows:
SMS Modem Configuration
1) Connect an SMS Modem through COM1 port or USB port according to need, and choose
Port Type
, the page will
display
Parameter
automatically;
2) Choose
SMS Modem
(GSM) according to the SMS Modem type;
3) Set the communication parameter of the SMS Modem;
4) Click the
Save
button to save the configuration of current user
’s SMS Modem.
Note
1. If the SMS Modem is connected through COM1 port, set the communication parameter of the SMS Modem as ‘9600,n,8,1’
before using it, the setting procedures are as follows:
2. If the SMS Modem is connected through USB port, use the default value of the communication parameter of the SMS Modem.
RDU Voice Notification System Setting
1) Type the server IP address in the
Server IP
field;
2) Type the port number in the
Port
field, and the default is 13393;
3) Click the
Save
button to save the voice notification system setting.
Email Server Configuration
1) Type the server IP address or domain name in the
Email Server
field;
2) Type the
Server Port
,
Email User
,
Email Password
and
Sender Email Address
in the corresponding fields;
3) Click the
Save
button to save the configuration of current user
’s Email server.
Note
1. The
Server Port
is 25 by default. When SSL is chosen, the
Server Port
will become 465 automatically;
2. The
Email User
is RDU-A by default;