1.5
Configurations for Liebert RX Installation
The Liebert RX can be installed in any of five configurations. Installation will vary depending on
the chosen configuration.
•
Configuration 1—Single unit
•
Configuration 2—Two units attached back-to-back
•
Configuration 3—Two units attached side-by-side
•
Configuration 4—Three units: two attached back-to-back with the third attached to one side
•
Configuration 5—Four units: two units attached back-to-back with one unit attached to each side
1.5.1
Configuration 1—Single Unit
This single-unit configuration is 24" (610mm) wide and 12" (305mm) deep. It must be secured to a
wall, rack or other structure. The required front service access is:
•
36" (914 mm) for units up to 150V to ground
•
42" (1067 mm) for units over 150V to ground
1.5.2
Configuration 2—Back-to-Back
This two-unit configuration is attached back-to-back and is 24" (610mm) wide and 24" (610mm)
deep. The two units can be can be installed in place of a floor tile. Remove one 24" x 24" (610 x
610mm) floor tile and position the Liebert RX over the opening, the unit will rest on top of the
raised floor cross members on all four sides. Refer to
Figure 2
.
1.5.3
Configuration 3—Side-By-Side
This two unit configuration is attached side-by-side and is 48" wide and 12" (305mm) deep. The
units must be secured to a wall, rack or other structure. Refer to
Figure 2
.
WARNING
Risk of heavy unit falling or tipping over. Can cause property damage, personal injury or
death.
The Liebert RX is not designed to be a free-standing unit in this configuration and may
present a tipping hazard. The Liebert RX must be properly supported until it is securely
attached to a supporting structure.
WARNING
Risk of heavy unit falling or tipping over. Can cause property damage, injury or death.
The Liebert RX is not designed to be a free-standing unit in this configuration and may
present a tipping hazard. The Liebert RX must be properly supported until it is securely
attached to a supporting structure.