LIEBERT® TDU 

TRANSFORMER DISTRIBUTION UNIT

Quick Installation User Guide

590-1811-501B/SL-23206_REV1

   

 1

SAVE THESE INSTRUCTIONS:

 

This manual contains important 

instructions that are to be followed 

during installation and 

maintenance of the TDU.

IMPORTANT:

 Before installing, 

connecting to supply or operating 

your Liebert TDU, please review 

the Safety and Regulatory sheet. 

INSTALLATION 
1.  Inspecting the TDU

Inspect the TDU for any signs 

of obvious damage. If damage is 

visible, do not proceed and call 

our warranty support line at 

1-800-222-5877 menu option 3, 

or email at microups.warranty@

VertivCo.com.

2.  Choosing a location

Install in a temperature-

controlled environment free of 

corrosive and conductive 

contaminants. Avoid locations 

near heat or water sources and 

exposed to direct sunlight. For 

proper ventilation, leave four 

inches clearance on all sides of 

the TDU. The input outlet should 

be nearby and easily accessible.

3.  Installing the TDU

The TDU may be installed in a 

rack by attaching the brackets 

to the TDU, installing the rail kit 

in the rack if needed, then 

installing into the rack. The 

TDU may also be installed in 

the vertical/tower orientation.

NOTE: 

This TDU is not for use in a 

computer room as defined in the 

standard for the protection of 

electronic computer/data 

processing equipment of ANSI/

NFPA 75.

CONNECTIONS
1.  Connecting Loads

There are two groups of five 

outputs, one on each side of 

the fan. Connect loads to each 

group not exceeding the group 

rating or breaker rating.  See 

Specifications.

2.  Connecting Input

Ensure that all the loads are 

first powered off. Connect the 

TDU input to only a Liebert 

UPS with an output voltage 

rated to 200-240VAC.

NOTE: 

When connecting to a 

Liebert® GXT4™ series UPS, the 

UPS must be configured to start on 

inverter. See the UPS User Guide 

for Instructions.

#

DESCRIPTION

1

NEMA L6-30  Input Cable

2

NEMA L6-20  Input Cable

3

Output Group 1

4

Output Group 2

5

NEMA 5-15/20 Output Receptacles

6

NEMA L5-20R Output Receptacles

7

NEMA L5-30R Output Receptacles

8

20A Output Breakers

9

30A Output Breakers

MODEL DESIGN CONFIGURATIONS