MAINTENANCE

Liebert Trinergy™ Cube

User Manual - 10H52243UM60 - rev. 6 - 12/2020

Page 23

6.  MAINTENANCE

Vertiv recommends that regular maintenance checks be carried out on-site by an authorized customer
service.

6.1.  Limited Life Components

The Trinergy™ Cube has a design life well in excess of 10 years. Well-maintained units can continue to
provide economic benefits for 20 years or more. Long-life components are used in the UPS wherever
practical and cost-effective. However, due to the currently available component material, manufacturing
technology  limitations and  the general  function  and  use  of  the  component,  a  few  components  in  the
Liebert UPS will have a shorter life cycle and require replacement in less than 10 years.
The following components utilized in the UPS have a limited life cycle and are specifically exempt from
warranty. To prevent a wear-out failure of one of these components affecting the critical load operations,
Vertiv  recommends  these  components  be  periodically  inspected  and  replaced  before  the  expected
expiration of their life cycle. The expected life of each component listed below is simply an estimate and
is  not  a  guarantee.  Individual  users  may  have  site-specific  requirements,  maintenance  and  other
environmental conditions that affect the length of the component’s useful life cycle.
Replacement components must exactly match the original component specifications.
For assistance with specific component specifications, replacement component selection and sourcing,
contact Vertiv technical support. For customers using Vertiv Services’ preventive maintenance services,
periodic inspection of these components is part of this service, as well as recommending component
replacement intervals to customers to avoid unanticipated interruptions in critical load operations.

Expected Life 

is sometimes referred to as 

Design Life.

6.2.  Disposal of batteries

When  the  useful  life  of  the  batteries  has  expired,  they  must  be  replaced  by  your  Customer  Service
representative. Exhausted batteries are classified as “harmful toxic waste” that must be disposed of in
accordance with the applicable regulations in the given country.

Note:
The typical useful life of the battery varies from three to five years, depending on ambient temperature
and usage.
Service addresses and telephone numbers can be found on the last page of this manual.

Component

Expected life

Replace in

Power AC Filter Capacitors

13 years

10-13 years

Power DC Filter Capacitors

13 years

10-13 years

Low-Profile Fans

8 years

6-7 years

Air Filters

1 to 3 years

Check Four Times per Year

Battery, Lithium Logic Memory Backup

10 years

8 to 9 years

Battery, Storage

Lead-Acid Wet-Cell (User Selection)

15 to 20 years

12 to 15 years

Valve-Regulated, Lead-Acid (VRLA)

5 years

2 to 3 years

10 years

3 to 4 years

20 years

8 to 12 years

Lithium-Ion

15 years

10 years

Summary of Contents for Liebert Trinergy Cube

Page 1: ...Liebert Trinergy Cube User Manual...

Page 2: ...Liebert Trinergy Cube UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52243UM60 rev 6...

Page 3: ...imilar methods even of parts are reserved Transgressors will be liable for damages All rights including rights deriving from patent license or registration of utility model or design are reserved Deli...

Page 4: ...13 3 1 Single UPS Switching to automatic operating mode 13 3 2 Single UPS Switching to system bypass 15 3 3 Parallel UPS system Switching to automatic operating mode 15 3 4 Parallel UPS system Switchi...

Page 5: ...Liebert Trinergy Cube Page 4 User Manual 10H52243UM60 rev 6 12 2020...

Page 6: ...ng the legal regulations of member states on electromagnetic compatibility superseding 2004 108 EC and successive amendments Conformity is established through compliance with the following standards I...

Page 7: ...4 Display Control panel that includes graphic symbols and data which show the status of the machine push buttons to operate the UPS 1 3 5 I O BOX The I O BOX is an enclosure that is part of the UPS a...

Page 8: ...el of power conditioning It protects the load from all types of electrical network disturbances that would use a greater amount of energy Efficiency at full load with the latest transformer free techn...

Page 9: ...ge 8 Figure 3 Dynamic Online High Efficiency Power Conditioning VI Battery operation In this operating mode the connected load is supplied from the batteries via the inverter In the event of a power f...

Page 10: ...supply system is located This temperature is used as a control parameter to set the maximum available output power limit Dynamically set means that the temperature is being used as the control parame...

Page 11: ...50 60 Hz or vice versa 2 3 Block diagram See Fig 6 on page 10 Legend QS1 PRIMARY MAINS INPUT SWITCH QS2 BYPASS RESERVE INPUT SWITCH QS3 MAINTENANCE BYPASS SWITCH QS4 OUTPUT SWITCH QS44 OUTPUT BYPASS...

Page 12: ...stem without interrupting the supply to the load Transfer to and from the maintenance operating mode must be done in accordance with para 4 3 on page 18 and para 4 4 on page 18 This operation may be c...

Page 13: ...anger operator safety and damage the system This operation must be carried out by authorized personnel and with the external battery disconnected Before closing the battery switch QS9 check that the p...

Page 14: ...witching to automatic operating mode With the Trinergy Cube system in bypass see Fig 7 on page 13 press the CONTROL button to switch to automatic mode Enter the Passcode in the pop up see Fig 8 on pag...

Page 15: ...Liebert Trinergy Cube OPERATING INSTRUCTIONS Page 14 User Manual 10H52243UM60 rev 6 12 2020 Figure 8 Passcode Figure 9 Stop or Start Inverter...

Page 16: ...TROL button on each of the UPS units in the parallel system and follow the same procedure as in para 3 1 on page 13 to switch them to the automatic operating mode All the UPS units will start in the V...

Page 17: ...s the load is supplied by the bypass and all automatic functions including battery operation are disabled 3 5 Operating mode selection In the default configuration Trinergy Cube can select any of the...

Page 18: ...n each Core to ON position 4 Wait for rectifier on each Core to ON position On the TS LCD the rectifier icon is green and the VDC is 700V 5 Switch QS44 to ON position 6 Switch QS2 to ON position Fans...

Page 19: ...FULL 5 Switch QS4_n on each Core to OFF position Fans on each Core OFF 6 Switch QS1 n on each Core to OFF position 7 Switch QS2 to OFF position 8 Switch QS44 to OFF position Fans on the BOX OFF 9 Swit...

Page 20: ...elded and must be run separately and distanced from the power cables The total length of these cables should not exceed 40m 5 3 Parallel switching procedures Procedures refer to para 2 3 on page 10 5...

Page 21: ...or all UPS 4 Switch QS4_n on each Core to OFF position all UPS Fans on each Core OFF 5 Switch QS1 n on each Core to OFF position all UPS 6 Switch QS2 to OFF position all UPS Fans on the BOX OFF 7 Swit...

Page 22: ...S Only in case of BOX in version FULL 3 Switch QS1 n on each Core to ON position all UPS 4 Wait for Rectifier on each Core ON position On the TS LCD the Rectifier icon is green and the VDC is 700V 5 S...

Page 23: ...Liebert Trinergy Cube PARALLEL OPERATION Page 22 User Manual 10H52243UM60 rev 6 12 2020 BLANK PAGE...

Page 24: ...eplacement components must exactly match the original component specifications For assistance with specific component specifications replacement component selection and sourcing contact Vertiv technic...

Page 25: ...ervice bypass Switch the UPS to maintenance bypass operation see Table 4 4 on page 18 6 4 Disconnect the batteries Open the external battery isolator or battery switch if present Before continuing mea...

Page 26: ...e bin symbol on the right is placed on this product to encourage you to recycle wherever possible Please be environmentally responsible and recycle this product at your local recycling facility at its...

Page 27: ...of Vertiv Co All other names and logos referred to are trade names trademarks or registered trademarks of their respective owners 2020 Vertiv Co All rights reserved Vertiv com Vertiv Infrastructure L...

Reviews: