ELECTRICAL FIELD CONNECTIONS
60kW, 600mm (24in.) MODEL
LIEBERT XDU
ELECTRICAL CONNECTIONS FOR OPTIONAL FEATURES
13)
LiquiTect shutdown and dry contact
(available when optional LiquiTect sensor is installed)
–
On LiquiTect
activation, normally open dry contact is closed across terminals 58 & 59 for remote indication. The LiquiTect
sensor notifies iCOM
TM
of indication through terminals 60 & 61. 1 AMP, 24VAC max load. Use Class 1 field
supplied wiring.
14)
Customer alarm inputs -
Terminals for field supplied, normally closed contacts, having a minimum 75VA,
24VAC rating, between terminals 24, 50, 51, 55, or 56. Use field supplied Class 1 wiring. The terminals are
available for customer alarm inputs, such as; smoke sensors and building fire alarms.
NOTE: Refer to specification sheet for total unit full load amps, wire size amps and max overcurrent protective
device size.