6.5.4 Draining the System
Vertiv recommends storing decommissioned units in spaces with temperatures that are above freezing in order to prevent
any remaining water from freezing in the unit.
Before moving the XDU, drain the fluid from the system through the customer connection points at the bottom of the unit.
Additionally, drain water from both pumps via the drain port located at the bottom of each pump housing.
NOTICE
Risk of piping system corrosion and freezing fluids. Can cause leaks resulting in equipment and expensive
building damage. Cooling coils, heat exchangers, and piping systems are at high risk of freezing and
premature corrosion. Fluids in these systems must contain an inhibitor to prevent premature corrosion.
The system coolant fluid must be analyzed by a competent fluid treatment specialist before start up to
establish the inhibitor level and evaluated at regularly scheduled intervals throughout the life of the system to
determine the pattern of inhibitor depletion. The fluid complexity and variations of required treatment
programs make it extremely important to obtain the advice of a competent and experienced fluid treatment
specialist and follow a regularly scheduled coolant fluid system maintenance program.
Fluid chemistry varies greatly as do the required additives, called inhibitors, that reduce the corrosive effect of
the fluids on the piping systems and components.
The chemistry of the coolant fluid used must be considered because some sources may contain corrosive
elements that reduce the effectiveness of the inhibited formulation. Sediment deposits prevent the formation of
a protective oxide layer on the inside of the coolant system components and piping. The coolant fluid must be
treated and circulating through the system continuously to prevent the buildup of deposits and/or growth of
bacteria. Proper inhibitor maintenance must be performed to prevent corrosion of the system.
Consult fluid manufacturer for testing and maintenance of inhibitors.
Commercial grade coolant fluid is generally less corrosive to the common metals of construction than water
itself. It will, however, assume the corrosivity of the coolant fluid from which it is prepared and may become
increasingly corrosive with use if not properly inhibited.
Vertiv recommends installing a monitored fluid detection system that is wired to activate the automatic
closure of field installed coolant fluid supply and return shut-off valves to reduce the amount of coolant fluid
leakage and consequential equipment and building damage. The shut-off valves must be sized to close off
against the maximum coolant fluid system pressure in case of a catastrophic fluid leak.
6 Piping Requirements
33
Summary of Contents for Liebert XDU 060
Page 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Page 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Page 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Page 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...