background image

LIEBERT® OUTDOOR CONTROL ENCLOSURE™

Quick Installation Guide

  

590-1734-501A/SL-10060_REV5_9-17

  

•  Install extra-low-voltage control 

wiring (24 V) from Terminals 

70 and 71 on the wire raceway 

in the compressor 

compartment of the indoor unit 

to Terminals 70 and 71 of the 

control enclosure.

•  Install extra-low-voltage control 

wiring between Terminals 

24 and 50 from the control 

enclosure to the indoor cooling 

unit’s common alarm or other 

alarm location for loss-of-flow 

indication.

•  Install extra-low-voltage control 

wiring between the auxiliary 

terminals on the control panel 

to Terminals 70 and 71 on the 

drycooler.

•  Connect the  flow switch wiring 

to Terminals 77 and 74.

•  Provide line voltage to power 

block(s) in the control 

enclosure as shown in the 

electrical schematic.

•  Install optional field-supplied 

disconnect if desired.

•  Run 3 -phase line voltage from 

the control box to each 

individual pump motor.

FLOW SWITCH 

INSTALLATION

NOTE:

 Only required for dual-

pump package installation.

•  Mount the flow switch in a 

section of coolant supply/

return piping where there is a 

straight run of at least five (5) 

pipe diameters on each side of 

the flow switch.

•  Mount the switch so the 

terminals or wire leads are 

easily accessible for wiring.

•  Mount the flow switch in a 

standard 1-in. x 1-in. x 1-in. tee 

for one -inch pipe installation. 

Use a reducing tee for larger 

sizes of pipe to keep the flow 

switch near the pipe and to 

provide adequate paddle 

length in the flow stream.

•  Screw the flow switch in 

position so the flat part of the 

paddle is at a right angle to the 

flow. The arrow on the side of 

the case must point in the 

direction of the flow.

•  The flow switch must be 

mounted in a horizontal 

pipeline.

DUAL PUMP CONTROLS 

SEQUENCE OF OPERATION

On a call for cooling, the 

compressor contactor and/or the 

Econ-O-Coil relay in the Liebert 

unit is energized. The relay and 

contactor are in the Liebert indoor 

evaporator section. Each 

compressor contactor has a side 

switch wired in parallel with the 

Econ-O-Coil relay and is 

responsible for closure of the 

low-voltage pump-control circuit.
This low-voltage circuit has a series 

of contactors, relays, selector 

switch and a flow switch. This 

circuit controls the start of the 

pumps and provides contact 

closure to interlock the 

drycooler(s) control circuit. Once 

the circuit is closed, 24V is passed 

to the pumps control circuit and 

the auxiliary relays are energized, 

closing the drycooler(s) control 

circuit.
Pump P1 is factory set to be the 

primary pump (Selector Switch 1-2). 

Voltage then passes through the 

normally closed contacts of the R2 

relay (standby pump relay), through 

the current overloads and to the #1 

pump contactor. At this point, the 

#1 pump and appropriate 

drycoolers are running.

When the pump establishes flow, it 

opens the system flow switch. The 

pump has approximately 

10 seconds to establish full flow. If it 

does, the system will run in this 

state until the call for cooling is 

satisfied and the circuit drops out. 

If this pump cannot establish flow 

or if it has been running and fails, 

the flow switch will close and 

energize an adjustable relay, 

typically set for 10 seconds.
Once this relay times out, it 

energizes the R2 switch over relay. 

This relay will drop out the voltage 

to the #1 pump contactor and 

energize the #2 pump contactor. 

Along with the R2 relay the AL 

relay (alarm relay) will energize. 

This will provide a set of closed 

contacts for remote indication of 

the switch-over situation.
Once the problem with the lead 

pump is repaired, the controls must 

be reset. To reset the control box, 

turn Off the main power to the 

control box and then restore the 

main power to the control box. 

Pump P1 then becomes the 

primary pump again.

Summary of Contents for Liebert

Page 1: ...witch and earth ground to unit per NEC CEC and local codes as applicable Failure to comply can cause injury or death NOTICE Risk of water leaks Can cause equipment damage NOTE To flush mount the back of the enclosure the adjustable brackets can be inverted Refer to the Dimensions drawings on the following page NOTE Alternate mounting locations are on a secure wall or building surface Use the provi...

Page 2: ...t have to be the same voltage as the Liebert indoor unit This separate power source may be 110V 208V 230V 460V or 575V single phase or three phase 60Hz or it may be 200V 230V 380V or 415V single phase or three phase 50 Hz as appropriate Extra low voltage Control Wiring Control interlock between the control enclosure and the indoor unit s or other source s is required Multiple indoor units may be c...

Page 3: ...ll for cooling the compressor contactor and or the Econ O Coil relay in the Liebert unit is energized The relay and contactor are in the Liebert indoor evaporator section Each compressor contactor has a side switch wired in parallel with the Econ O Coil relay and is responsible for closure of the low voltage pump control circuit This low voltage circuit has a series of contactors relays selector s...

Page 4: ...missions Specifications are subject to change without notice LIEBERT OUTDOOR CONTROL ENCLOSURE Quick Installation Guide 4 1734 501A SL 10060_REV5_9 17 TECHNICAL SUPPORT AND SERVICE Vertiv Services Inc 24x7 dispatch of technicians for all products 1 800 543 2378 Liebert Thermal Management Products 1 800 543 2778 Liebert Channel Products 1 800 222 5877 Liebert AC and DC Power Products 1 800 543 2378...

Reviews: