Figure 3.8 Connectors on the EXL S1 EIB
Item
Description
1
TB3 (24VDC option power)
2
TB1154 (BIB interface)
3.6.2 Connecting to Liebert EXL
Connect to TB1154 of the EXL control drawer, see Figure 3.9 on the next page.
Terminal block
Pin
Connects to
(desribes external item)
Maximum Voltage
Maximum Current
TB1154
1
CAN +24V
24VDC
2A
2
CAN Common
3
CANbus High
4
CANbus Low
Table 3.2 EXL control contacts to BIB