Vertiv
|
NetSure™ 2100 Series -48 VDC Power System Installation Manual (IM582138000)
|
Rev. C
59
WARNING!
The intra-building port(s) of the equipment or subassembly is suitable for connection to
intra-building or unexposed wiring or cabling only. The intra-building port(s) of the equipment or
subassembly MUST NOT be metallically connected to the interfaces that connect to the OSP or its
wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as
described in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The addition
of Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP
wiring.
The intra-building port (RJ-45) of the equipment or subassembly must use shielded intra-building
cabling/wiring that is grounded at both ends.
Figure 34:
Mini Control Unit Second Ethernet Port Located on External IB4 Assembly
10M Ethernet
Port (RJ-45)
LAN Connection
Top Cover
Removed
10M Ethernet
Port (RJ-45)
LAN Connection
External IB4 Controller
Interface Board Kit,
P/N 559239