NOTE!
Only reset the battery capacity when the battery is fully charged; otherwise, the battery charge
status may not be accurate.
Local Menu Navigation:
Main Menu / Settings / Batt Settings / Reset Batt Cap.
Web Menu Navigation:
Settings Menu / Battery Tab / Reset Battery Capacity.
Refer to the Mini Control Unit Instructions (UM1M831ANA) for detailed instructions.
Configuring the Mini Control Unit Identification of Rectifiers and Assigning which Input Feed is
Connected to the Rectifiers
When rectifiers are all installed prior to applying power and starting the system, the order in which the Mini
Control Unit identifies the rectifiers is by serial number (lowest serial number is Rect 1, next lowest is Rect 2,
etc.). If you prefer the Mini Control Unit to identify the rectifiers by position in the system, perform the following
procedure.
Upon power up, the Mini Control Unit arbitrarily assigns Feed AC1, AC2, or AC3 to each rectifier. This
assignment is used to display rectifier AC input feed voltage(s). The User may reassign the feed to each
rectifier per your specific installation by following the procedure below.
Local Menu Navigation:
None.
Web Menu Navigation:
Refer to the Mini Control Unit Instructions (UM1M831ANA) for detailed instructions.
Checking System Operation
Mini Control Unit Alarm Relay Check
The following procedures can be used to verify operation of the external alarm relays in a power system
equipped with a Mini Control Unit with the factory default configuration. Note that alarm relays on a Mini
Control Unit with a custom configuration may operate differently.
NOTE!
There are two methods to check alarm relays. The first is by actually causing an alarm. The
second is by using the Mini Control Unit alarm relay check function. The first method is used in the
following procedures.
Checking the AC Fail Alarm
Procedure
NOTE!
Battery must be connected during this procedure.
1.
Verify system is operating and no alarms are present.
2.
Verify the Mini Control Unit displays the Main Menu. If not, press ESC repeatedly to return to the Main
Menu.
3.
Open the external AC disconnect(s) or protective device(s) that supply power to all of the rectifier
modules.
a)
Requirement:
An audible alarm sounds. Alarm will be silenced in Requirement d.