Vertiv™ NetSure™ 211 SERIES -48 VDC Battery Cabinet Installation & User Manual (Section 6023)
|
Rev. L
13
Figure 6:
Mounting the Battery Cabinet to a Wall
Connecting Battery Cabinet(s) to the Associated Power System
Battery Leads
Cables with connectors are provided on the associated power system and the battery cabinet to allow simple
interconnections between a battery cabinet and the associated power system and between battery cabinets.
The battery cabinet is designed to be daisy-chained together with additional battery cabinets. There is no limit
to the number of battery cabinets that can be connected together. However, a maximum system current of
30 A should be maintained regardless of the number of interconnected battery cabinets.
Procedure
NOTE!
as this procedure is performed.
1.
Connect the power system’s battery cable terminated in an Anderson connector to the first battery
cabinet’s battery cable terminated in a mating Anderson connector.
2.
Connect the second battery cabinet’s battery cable terminated in an Anderson connector to the fixed
mating Anderson connector located on the first battery cabinet.
3.
Repeat the above step if there are additional battery cabinets.
Customer-supplied
mounting hardware
WALL
Two 0.406”
mounting holes