Vertiv™ NetSure™ 211 SERIES -48 VDC Battery Cabinet Installation & User Manual (Section 6023)
|
Rev. L
11
Relay Rack Method
Procedure
1.
and install the 19” or 23” relay rack mounting angles to the battery cabinet. Mounting
hardware is provided with the battery cabinet. Torque these connections to 46 in-lbs.
NOTE!
There are three mounting locations for the mounting angles providing different projections in
front of the relay rack.
Figure 3:
Installing Mounting Angles on the Battery Cabinet
2.
Install battery retention strap through openings in rear of cabinet. Orient the buckle per
3.
Secure the battery cabinet to the relay rack with the provided 12-24 x 1/2” hex head thread-forming
screws (six per side) (P/N 218710500) and #12 ground washers (three per side) (P/N 215640600).
Torque these connections to 35.0 in-lbs.
Wall Method
WARNING!
Ensure the technique and hardware used in securing the battery cabinet can support the
total weight of the battery cabinet and the four (4) batteries. Refer to “Batteries” on page 9 for a battery
weight reference table. If being mounted to a stud wall, the cabinet must be fastened to the studs.
Failure to mount the cabinet correctly may result in serious personal injury or equipment damage.
Procedure
1.
Ensure that connector, wires and bushing located at the back are moved to the side, as shown in
, before mounting the cabinet.
2.
Install battery retention strap through openings in rear of cabinet. Orient the buckle per