Vertiv™ NetSure™ 211 SERIES -48 VDC Battery Cabinet Installation & User Manual (Section 6023)
|
Rev. L
14
Figure 7:
Connecting Multiple Battery Cabinets
Battery Disconnect Circuit Breaker Alarm Leads
Procedure
1.
Furnished with the battery cabinet are battery disconnect circuit breaker alarm lead assemblies. Refer
to the power system installation manual to use these alarm leads to connect the battery cabinet battery
disconnect circuit breaker alarm into the power system alarm circuits.
NOTE!
Supplied with the battery cabinet is a yellow alarm lead assembly P/N 545696 and an orange
alarm lead assembly P/N 565513. P/N 545696 is always used. P/N 565513 is used only with power
systems containing a 1M831ANA Mini Controller (may be discarded if battery cabinet is used with other
systems).
POWER SHELF
BATTERY CABINET
MAIN
BATTERY CABINET
SUPPLEMENTAL
(OPTIONAL)
BATTERY CABINET
SUPPLEMENTAL
(OPTIONAL)