Vertiv
|
NetSure -48V DC Bulk Output Power System Installation and User Instructions (UM582127100)
|
Rev. E
11
SYSTEM OVERVIEW
Customer Documentation Package
This document (UM582127100) provides Installation and User Instructions for NetSure™ -48V DC Bulk Output
Power System Model 722NBBB, Spec. No. 582127100.
The complete Customer Documentation Package consists of…
NetSure™ -48V DC Bulk Output Power System Installation and User Manual
•
Power System Installation and User Instructions: UM582127100
NetSure™ NCU Controller User Manual
•
NCU Controller User Instructions: UM1M830BNA
USB Drive with All Customer Documentation
•
Power System Installation and User Instructions: UM582127100
•
Power System “System Application Guide”: SAG582127100
•
Rectifier Module Mounting Shelf Power Data Sheet: PD588705000
•
Rectifier Instructions: UM1R483500E
•
NCU Controller User Instructions: UM1M830BNA
•
Engineering Drawings
•
Also provided on the USB drive is a controller configuration drawing and the controller configuration
files loaded into the controller as shipped.
System Description
-48V DC @ up to 2000 Amperes Bulk Output Power System
The NetSure™ 722NBBB Bulk Output Power System is intended for use to expand or replace legacy -48V DC
rectifiers while retaining the distribution power board. It can be used with any -48V DC power system,
regardless of vendor or plant type.
The 722NBBB is an integrated power system containing rectifiers, intelligent control, metering, and monitoring.
This power system is designed to power a load while charging a positive grounded battery. This power system
is capable of operating in a batteryless installation or off battery for maintenance purposes. The power system
is designed for operation with the positive output grounded.
This system consists of the following components.
Main Rectifier Module Mounting Shelf
The system contains a main rectifier module mounting shelf. This shelf houses up to five (5) rectifier modules,
the controller, a controller interface board, and a system interface board. Refer to Power Data Sheet
PD588705000 for more information.
NCU (NetSure Control Unit): The controller provides power system control (including optional low voltage
battery disconnect (LVBD) and low voltage load disconnect (LVLD) control), rectifier control (including a
charge control function), metering functions, monitoring functions, and local/remote alarm functions. The