BASIC RACK PDU 

 

 
 

Specifications 

 

Overview 

 

The Vertiv  Basic Rack PDU products are Power Distribution units (PDU) intended for connection 
to a 30 Amp AC Mains circuit.  The PDUs are designed to be powered by a single phase AC input 
circuit.  The Vertiv Basic Rack PDUs covered by this manual are available in vertical or horizontal 
configurations  rated  208-240V  and  can  be  optionally  configured  with  a  Vertiv  Power  Meter  that 
provides local monitoring and display of Current, Voltage, Wattage, and Power Factor.   

 

Environmental 

 

Temperature 

 

Operating:

 

10°C (50°F) min  

45°C (113°F) max 

 

Storage:

 

-25°C (-13°F) min     

65°C (149°F) max 

 

Humidity 

 

Operating:

 

5% min 95% max

 

(non-condensing) 

 

Storage:

 

5% min 95% max

 

(non-condensing) 

 

Elevation 

 

Operating:

 

0 m (0 ft) min

 

2000 m (6561 ft) max 

 

Storage:

 

0 m (0 ft) min

 

15240 m (50000 ft) max 

 

Electrical 

 

See nameplate for unit ratings. 

 

Receptacle Ratings 

 

NEMA 5-15R or L5-15R 

125 Volts, 15 Amp 

NEMA 5-20R or L5-20R 

125 Volts, 20  Amp 

NEMA 6-20R or L6-20R 

250 Volts, 20  Amp 

IEC-320 C13 

125/250 Volt, 15 Amp (per Receptacle Bank) 

IEC-320 C19 

125/250 Volt, 20 Amp 

 

EMC Verification 

 

This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following 
two  conditions:  (1)  This  device  may  not  cause  harmful  interference,  and  (2)  this  device  must 
accept any interference received, including interference that may cause undesired operation. 

 

This Class A digital apparatus complies with Canadian ICES-003. 

 

Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. 

 

Warning: Changes or modifications to this unit not expressly approved by the party responsible for 
compliance could void the user’s authority to operate this equipment. 

Summary of Contents for VP7541

Page 1: ...Instruction Manual Basic Rack PDU VP7541 and VP9571A VertivCo com geist ...

Page 2: ...re 3 Humidity 3 Elevation 3 Electrical 3 Receptacle Ratings 3 EMC Verification 3 Installation 4 Instructions 4 Guidelines 4 Mounting 5 Optional Local Monitoring 12 Power Meter 12 Current Meter 12 Service Tech Support 13 Service and Maintenance 13 More Technical Support 13 ...

Page 3: ...000 m 6561 ft max Storage 0 m 0 ft min 15240 m 50000 ft max Electrical See nameplate for unit ratings Receptacle Ratings NEMA 5 15R or L5 15R 125 Volts 15 Amp NEMA 5 20R or L5 20R 125 Volts 20 Amp NEMA 6 20R or L6 20R 250 Volts 20 Amp IEC 320 C13 125 250 Volt 15 Amp per Receptacle Bank IEC 320 C19 125 250 Volt 20 Amp EMC Verification This Class A device complies with part 15 of the FCC Rules Opera...

Page 4: ...he effect that overloading of the circuits might have on over current protection and supply wiring The PDU relies on the building installation for protection from over current conditions A certified overcurrent protection device is required in the building installation The overcurrent protection device should be sized according to the PDU s nameplate ratings and local national electrical codes Rel...

Page 5: ...BASIC RACK PDU 5 Mounting Full Length Bracket Using the full length bracket mount PDU to rack as shown Mini L Brackets SLB 4 ...

Page 6: ...al Extension Brackets VCB 1 Using the vertical extension brackets attach PDU to rack as shown Toolless Mounting Hardware 11621 Secure toolless mounting buttons to PDU as shown Use toolless buttons with key holed slots built into cabinet or with optional Vertiv key holed brackets ...

Page 7: ...acket TLFL Using full length toolless bracket and toolless mounting buttons attach PDU to rack as shown Single Side Mount 2 Unit Brackets TSMX2 Using single side mount 2 unit brackets and toolless mounting buttons attach PDU to rack as shown ...

Page 8: ...BASIC RACK PDU 8 Offset Side Mount Brackets EZB 1 Using the offset side mount brackets attach PDU to rack as shown 7 Extension Brackets XB 7 Using the 7 extension brackets attach PDU to rack as shown ...

Page 9: ...BASIC RACK PDU 9 Flush Mount Brackets FM Using flush mount brackets attach PDU to rack as shown Adjustable Mount Brackets AM Using adjustable mount brackets attach PDU to rack as shown ...

Page 10: ...ASIC RACK PDU 10 Panel Mount Brackets PM Using panel mount brackets attach PDU to rack as shown 23 Conversion Mounting Brackets 23 RM Using conversion mounting brackets attach 19 PDU to 23 rack as shown ...

Page 11: ...able Mount Bracket CMB 1 Attach cable mount bracket to PDU as shown use tie wraps to secure cords to bracket 19 Horizontal Panel Mount Brackets 7938 Using the 19 horizontal panel mount brackets attach PDU to rack as shown ...

Page 12: ...ured in true RMS Amps Voltage PDU output voltage measured in true RMS Voltage Power PDU output power measured in Watts referred to as real or active power Power Factor Ration of real PDU output power to apparent PDU output power Power Meter Display Real power is the power in a circuit that is transformed from electric to non electric energy while apparent power is the total power supplied to the c...

Page 13: ...U or you may void the warranty No serviceable parts inside It is recommended that power be removed from the unit before installing or removing any equipment More Technical Support VertivCo com geist Phone Support 1 800 432 3219 Email support VertivCo com or contact your distributor Technical Support Form vertivco com Tech Support ...

Page 14: ...BASIC RACK PDU 14 Thank You For Purchasing Your Vertiv Product VertivCo com geist ...

Reviews: