background image

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 15 60 60  Fax: 02380 261204  E-mail: vesltd@ves.co.uk Web: www.ves.co.uk

ecovent 

NRG

 Air Handling Units

Installation, Operation and Maintenance Manual

9

Continued

Steam coils are suitable for use with saturated steam up to 100psi. The pipe work must be so
arranged to provide adequate drain lines with a suitable strainer and steam trap. All steam and
drain lines should be lagged. The supply should be taken from the top of the steam main, to
avoid the introduction of moisture or air into the coil. The pipe shall be arranged so that it does
not interfere with the coil expansion. Where steam coils are fi tted it is essential that a time delay
is installed in the fan starter control circuit. The fan shall be kept running for at least two minutes
after the steam supply to the coils has been shut off, so that residual heat of the coil is dissipated.
If the pipe run is unduly long and prone to water logging, it should be properly trapped, just
before the coil.
If the steam is from a high pressure steam main, it is essential to have a working pressure relief
valve on the low side to ensure that dangerous overheating of the air and excessive pressure
cannot occur. Fitting a frost thermostat at the unit inlet and ensuring that boilers run
continuously in low ambient temperatures can prevent this.

All cooling coils have fully boxed and insulated cases, with moisture eliminators fi tted as
standard. The drain pan will require trapping to the drain line, for further information please
see 

VES Ref. ID665

. DX and Condenser Coils must be connected to systems in accordance with 

accepted refrigeration codes of practice and if fi tted upstream to steam or water coils, care must be 
taken to ensure that the air temperature does not drop below 0°C.
For units supplied with condensing units, refer to the appropriate supporting documentation.

Installation

Coils

DX Cooling Coils

Typical DX Cooling Coil

Fig.

Typical Steam Coil

Fig.

Airfl ow

Return

Flow

4

Airfl ow

Liquid

Suction

Eliminators

Drain

Airfl ow

Return

Flow

Drain

Air vent

Typical LPHW Coil

Fig.

Steam Coils

Summary of Contents for ecovent NRG

Page 1: ...ic current and high voltages Indicates hazards that require safety advice for personnel and or potential unit property damage Indicates important information Page Introduction 1 Nomenclature 2 Receipt...

Page 2: ...Null Single Skinned DS 25mm double skinned mineral wool in ll PB 25mm double skinned plasterboard in ll EE 50mm double skinned mineral wool in ll 10 Handing RT Right Top Access denotes position of RB...

Page 3: ...ided in accordance with Health and Safety and Building Regulations For con rmation of required access please see the appropriate unit outline drawing note that some access doors are hinged For optimum...

Page 4: ...rods If required the unit can be further secured to the oor via knockout xings holes on the feet xings to be supplied by others Standard units should be mounted in the horizontal plane level with lid...

Page 5: ...move the four support covers as shown retaining the screws Take especial care when working around the speed controller section Remove the heat exchanger carefully lifting straight up and out taking ca...

Page 6: ...hanger and silicon into place along upright angles Turn the drain pan over so that the drain sump now faces the heat exchanger upside down and replace in the unit making sure that the drain is adjacen...

Page 7: ...is the correct way up taking special notice on bottom access units Slide the pump down onto the bracket as shown Fit the pump sensor in the drain pan sump as shown Secure the sensor into place using s...

Page 8: ...ant local codes of practice Where threaded con nections are supplied the only approved method of jointing method is by use of Boss white and hemp The thread tted to the coil is to be supported at all...

Page 9: ...and prone to water logging it should be properly trapped just before the coil If the steam is from a high pressure steam main it is essential to have a working pressure relief valve on the low side to...

Page 10: ...for special versions of the units consult the wiring diagram in your document pack or contact our customer services department on 08448 15 60 60 quoting the sales order SO number and unit type as foun...

Page 11: ...C A C400V F 2 ZB501 0 40 1 70 4 50 8 3 SNS641 0 49 2 20 5 00 10 4 SNS641 0 49 2 20 5 00 10 5 SNS741 0 73 3 30 7 00 12 6 SNS841 1 30 5 70 15 0 30 Model 400V 3PH 50Hz ecoNRG Unit Fan Motor Power kW FLC...

Page 12: ...d controller documentation for further operational details Units size 7 8 and 9 are supplied with tted 3phase inverters for fan speed control and commissioning see the accompanying inverter documentat...

Page 13: ...ted to the air volume via the energy conservation rate as per the graph below Simply read across from the pressure measurement to the appropriate fan curve and down to calculate the resultant air volu...

Page 14: ...avily soiled or damaged in any way they should be replaced The fan impeller should be cleaned every 6 months Failure to clean the fan on a regular basis could result in loss of fan performance or caus...

Page 15: ...RG air handling units Type NRG Manufacturer VES Andover Limited The product above is produced in accordance with EC Council Directives 2004 108 EC Electromagnetic Compatibility Directive 2006 95 EC Lo...

Page 16: ...12 24 months from the date of dispatch This can be covered at a cost of just 3 of order value minimum charge 50 00 Option 3 12 36 Month Extended Warranty 12 36 months from date of dispatch For this c...

Reviews: