Front-Panel Menu 4
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
55 of 146
Front-Panel Controls
Access Level 2 operates the following front-panel button-controls:
•
Alarm Silence
•
Re-sound Alarm
•
Reset
•
Fire Drill
•
Programmable Function
Obtain Access level 2 with the menu-password or with the Enable Access key.
Reference “Section 2, Overview” for a summary of these controls and “Appendix E, Operating Instructions”
for detailed functional descriptions.
Alarm Silence
The Alarm Silence button silences the internal buzzer as well as sounders connected to the Elite-RS Panel.
Press the Panel Sounder Silence button to silence the internal buzzer without silencing sounders on the entire
network.
Re-Sound Alarm
The Re-Sound Alarm button re-sounds the alarm following a silence condition initiated by the Panel Sounder Silence
or Alarm Silence command.
Reset
The Reset button clears latching inputs on the control panel. Latching inputs remain active after correcting the cause
of the input event. Perform a reset to clear latching inputs on the control panel caused by supervisory, trouble,
pre-alarm and fire signals. Non-latching inputs do not require reset. Non-latching inputs clear after correcting the
cause of the input condition.
Fire Drill
The Fire drill button initiates a fire drill on the control panel. Cancel the fire drill by pressing the Fire Drill button
while in Access Level 2. The Fire Drill button can also be configured for specific functions with eSP Discovery.
Programmable Function
The Programmable Function button is disabled as a default condition, but can be configured to perform specific
functions while in Access Level 3, eSP Discovery or Loop Explorer. Operate the Programmable Function button in
Access Level 2 of the Elite-RS Panel menu.
CAUTION!
Pressing the Alarm Silence button silences sounders on the entire network.