Equipment list B
VES, LLC
Elite-RS Panel Installation Manual VF3529-00, Revision E01.03
H-Series
77 of 145
Synchronization
NAC channels 1 and 2 of the Elite-RS Panel provide single and dual circuit synchronization. Single circuit
synchronization provides synchronized NAC outputs on one channel of the Elite-RS Panel. Dual circuit
synchronization provides synchronized NAC outputs on two channels of the Elite-RS Panel.
NAC synchronization can be performed on individual Elite-RS Panels.
NAC synchronization cannot be performed on between multiple Elite-RS Panels.
Configuring NAC Outputs
Settings are provided in eSP Discovery and Loop Explorer for controlling the NAC outputs of the Elite-RS Panel.
Selections are available in these utilities for providing outputs with synchronization or various forms of constant
power. Settings are also provided to allow the Alarm Silence button to operate on the front-panel in various modes.
NAC channels of the Elite-RS Panel can be configured as independent outputs as long as the same manufacturer
types are used when operating synchronized outputs.
Strobe operations are disabled as default functions on the Elite-RS Panel. Settings are available to enable the
operation of sounders and strobes when operating NAC channels in the constant power mode.
Review the settings described below to configure each NAC output for operation: .
Output Options
General Alarm and Emergency are selected as default conditions. Alternative output options
for this field include Auxiliary Output, Pre Alarm Output, Supervisory Alarm, Trouble and
Security Output.
Do not select the General Alarm option if the NAC channel is to be controlled by cause and
effect programming.
Strobe
Strobe Output is not selected for operation as a default condition. Selecting this field
allows the user to define which synchronization protocol to be used.
NAC Aux 24 DC
When the Strobe option above is not selected, Off is selected as the default operating condi-
tion. Options for this output are continuous constant power, door holder continuous power
and resettable constant power. Continuous constant power provides a voltage output
identical to Aux 24 VDC. Door holder continuous power drops out during fire alarm
conditions or when an AC fail event occurs. Resettable constant power drops out between
four and five seconds after the reset of the control panel.
Alarm Silence
Each NAC circuit is configurable in reaction to the Alarm Silence button on the front-panel of
the Elite-RS. Edit properties of the NAC channel in Loop Explorer or eSP Discovery.
Select the box for Silencing if NAC silencing is required on this channel. If Internal
Synchronization Protocols are in use, an option is also available to Silence the strobe.
Failure to check the Strobe Silence box will cause horns to be silenced with continued
operation of the strobe.