Installation 3
VES, LLC
eView Installation Manual VF3510-00, Revision E01.06
11 of 16
Figure 3-1 illustrates surface and flush-mounting positions of the eView:
Figure 3-1
Mounting Positions
Connecting the Circuit Board
Terminate all wiring connections at the single row of terminals located along the bottom of the eView circuit board.
Shielded fire alarm cable such as FP200 and metal-cable-connectors must be used for all connections. The resistance
of any conductor of the data cable must not exceed 25 ohms. The shield of the cable must be connected securely to
the enclosure and to the metal-cable-connector.
Wiring
Wiring should enter the cabinet at the knockouts provided at the back and top of the enclosure. Wiring must not cross
the front of the eView circuit board. Wiring must be dressed away from the eView circuit board when cabling enters
the enclosure at locations other than the knockouts.
Data Termination
Up to 15 devices can be connected to an eLAN or Elite Panel. In and out terminals for data and 24V DC are
provided on each device. All devices are supplied with a push-on-jumper at position J3 on the left of the PCB. This
jumper connects a terminating resistor which needs to be in place for the last device on the data-line.
Remove all jumpers except the last device on the data-line if more than one device is connected.
If there is only one device connected then the jumper should be left in place.
The COMMS LED will flash quickly when a device is communicating with the eLAN or Elite Panel.
The COMMS LED will not illuminate when a device is disconnected on the eLAN or Elite Panel.
Secure the eView to a flat
surface using suitable wall
mounting hardware.