screwdriver in the large slot and twist, or use a small screwdriver in the side slots to lever the plug out.
l
Insert the pipes into the pipe inlet(s) ensuring a firm fit.
Note:
DO NOT glue the inlet pipes to the pipe inlet manifold.
When configuring the detector ensure that the correct pipes in use are selected as indicated in Table 3-1.
No. of Pipes
Preferred Pipe Inlet Port to use
Pipe 1
Pipe 2
Pipe 3
Pipe 4
VEP-A10-P
1
Inlet 2 or 3
Inlet 2 or 3
2
3
Inlet 1 or 4
Inlet 1 or 4
4
Table 3-1: Preferred use of pipe inlet ports
1
2
3
4
Figure 3-1: Pipe inlet port numbering
For code-specific information, refer to Codes and Standards Information for Air Sampling Smoke Detection on
page iii.
3.4
Managing the Exhaust Air
Air is expelled from the detector via the exhaust port at the bottom of the unit enclosure.
The air exhaust port is tapered to accommodate standard pipes of OD 25 mm (ID 21 mm) and to provide an
airtight seal. IPS ¾ inch pipes (1.05 inch OD) require an adaptor (VSP-961) as shown in Figure 3-2. If required,
connect an outlet pipe to the exhaust manifold. DO NOT glue this pipe to the exhaust manifold as this will void
the warranty.
Figure 3-2: Imperial Pipe Adaptor (VSP-961)
Where the detector is located outside the protected environment, it may be necessary to return the exhaust air
to the same environment. For example, where pressure differences exceed 50 Pa, or where hazardous
substances are present inside the protected environment. Return air pipes need to be as short as possible to
minimize the effect of airflow impedance in the return air pipe network.
Summary of Contents for VEP-A10-P
Page 2: ......
Page 10: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VEP A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 54: ...VESDA E VEP A10 P Product Guide 48 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VEP A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A10 P Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VEP A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 116: ...VESDA E VEP A10 P Product Guide 110 www xtralis com Z zone 59 61 79 105 ...