background image

98MANAL544   Rev. C    3/21/17 

BASIC OPERATION & INTERNAL CALIBRATION CIRCUIT

 

 (See Maintenance and Repair for calibration frequency recommendations.)  

Note:  

The casting of the module has raised numbers at the adjustment screw positions.  Those numbers 
reflect the following function of the assigned screw. 

Screw 1: Top Left, Coarse Zero Pot (CCW - Lower, CW - Raise) 
Screw 2: Top Right, Fine Zero Pot (CCW - Lower, CW - Raise) 
Screw 3: Lower Left, Internal Cal. Activation Pot (12 or 6 o’clock position – Disengage; 3 o’clock position - Engage) 
Screw 4: Lower Right, Span Adjustment Pot (CCW - Lower, CW - Raise)  
 

1.  Outside of using the calibration circuit or the availability of a metrology lab for obtaining a pressure 

(Full Scale) reading, no object should be used to physically move the sensor.  

2.  Once proper connections and power are applied, the unit should begin to function.  
3.  Check the zero output (4.00 mA) with the performance certificate to verify readings.  If it is out of 

specification from the performance certificate, use the coarse and fine zero adjustment screws to 
obtain the proper reading.  

4.  With no pressure applied, engage the calibration circuit by slowly rotating the calibration screw until 

the current output rises to about 8.80 mA’s.  Check the reading with the performance certificate.  If 
the reading is off, adjust the span screw to raise or lower the reading – return the calibration circuit to 
the original position.  

5.  When making zero and/or span adjustments, there may be some interaction between the zero and 

span readings - repeat adjustments if needed.  

6.  Always return the calibration screw to off or full CCW position before installing the transmitter into the 

application.  Note: This is a common reason for incorrect readings at start-up.  The calibration circuit 
must be deactivated in order for the product to perform properly.  

7.  Once the product has been tested and functionality verified, the power and meter connections may be 

removed and the product reconnected to the instrumentation loop.  

 

NON-STANDARD RANGE (NSR) CALIBRATION

 

NSR: A non-standard range is an alternate scaled reading as requested by the customer.  Through the 
use of a single transmitter, numerous pressure ranges can be set-up.  The Model 544 can be scaled 
down to any pressure range, from five times the original range.  Only NSR requests for ranges less than 
the sensor rated range are recommended and in most cases possible.  The NSR is possible due to the 
ability of the adjustment screws to alter where the zero and span will fall.  Refer to the below example for 
field NSR calibration.  

NSR EXAMPLE 

You have Viatran’s Model 544 with a standard range of 0 to 100 PSI.  You would like to set an NSR of 0 
to 50 PSI.  Refer to the Performance Certificate and obtain the following:  

Zero = 0 PSI = 4.00 mA 

Full Scale = 100 PSI = 20.00 mA 

Cal Value = 20.04 PSI = 8.81 mA 

In order to recalibrate the transmitter, you must determine the cal reading in mA’s at the NSR range.  This 
is done by  calculating what the cal output should be at the NSR range. For the example listed, the 
standard calibration value is set to represent 20.04 PSI.  Once internally set, the calibration (Cal) will 
always represent this pressure.  

Use the formula:  Cal mA’s =  [(16 x Standard Cal Pressure) / desired range] + 4 
Substitute Actual Numbers:  Cal mA’s = [(16 x 20.04) / 50] + 4 

Cal mA’s = (320.64 / 50) + 4 
 Cal mA’s = 6.413 + 4 Cal mA’s = 10.413 mA’s 

 The zero would be set for 4.00 mA’s, and the calibration circuit will read (after adjusting span) 10.413 
mA’s when activated.  This would provide a new NSR range for the unit of 4-20 mA’s over 0-50 PSI.  

Summary of Contents for 544

Page 1: ... Rev C 3 21 17 INSTALLATION DATA MANUAL MODEL 544 PRESSURE TRANSMITTER 199 Fire Tower Drive Tonawanda NY 14150 Int l 1 716 629 3800 Toll Free 1 800 688 0030 Fax 1 716 693 9162 www viatran com solutions viatran com ...

Page 2: ...should be compatible with 316 SS 5 Installation should occur only after electrical input power and line pressure is verified as being off and at zero 6 The product s internal electrical circuitry is isolated from case ground It is not recommended that the case or ground of the unit be connected to the input or output of the product or wiring system Ground loops and line noise will affect the produ...

Page 3: ...3 98MANAL544 Rev C 3 21 17 ...

Page 4: ...te This is a common reason for incorrect readings at start up The calibration circuit must be deactivated in order for the product to perform properly 7 Once the product has been tested and functionality verified the power and meter connections may be removed and the product reconnected to the instrumentation loop NON STANDARD RANGE NSR CALIBRATION NSR A non standard range is an alternate scaled r...

Page 5: ...sure to moisture or fluids at the electrical connection breather area model dependent will eliminate premature internal failure of the product Generally any time the product is removed from service the connector and pressure port threads should be cleaned and the pressure cavity flushed with a 316 stainless steel compatible cleaner to prevent media buildup It is suggested that the calibration be v...

Reviews: