Scanner With Control

1. Energize the control and check that the 

switch is not energized.

2. Press MANUAL RIGHT switch on control and hold until

the scanner rotates to the desired right-hand position.

Release pushbutton.

3. Install the right limit stop (2 on Figure 2) just to the right of

the switch actuator (4) by pushing it into the groove until
it snaps in place.

4. Press MANUAL LEFT on control and hold until the

scanner rotates to the desired left-hand position.

Release pushbutton.

5. Install the left limit stop (3) to the left of the switch

actuator as in step 3.

6. Mount camera on scanner. Refer to MOUNTING THE

CAMERA Section.

7. With both limit stops securely snapped in place, pan to

both stop positions and recheck for exact trim.

Scanner With Line Cord Option

 Plug line cord into AC outlet

2. Allow unit to 

 to desired right-hand position. Un-

plug cord.

3. Install the right limit stop (2 on Figure 2) just to the right of

the switch actuator (4) by pushing it into the groove until it
snaps in place.

VIEW A-A

2

Right Limit Stop

3 Left Limit Stop
4 Switch Actuator

 Hex-head Screws (2)

6 Camera Mounting Holes 

Figure 2

Limit Stop Adjustments

4. Plug in the line cord and allow the unit to 

 to

desired left-hand position. Unplug cord.

5. Install the left limit stop (3) to the left of the switch actuator

as in step 3.

6. Mount camera on scanner. Refer to MOUNTING THE

CAMERA section.

7. With both limit stops securely snapped in place, energize

the scanner and check for exact trim.

MOUNTING THE CAMERA

CAUTION: Do not mount an 

 lens on an autopanning

unit. Such use will cause excessive wear on the iris

mechanism 

as 

it constantly compensates for different light

levels.

Use a 

 screw and lockwasher to mount the camera.

To obtain the best balance, this screw must be placed in one

of three positions provided (6 on Figure 2). A simple method

to determine camera balance is to place a pencil under the
camera on a flat surface. Move the camera until it balances
on the pencil. The position of the pencil under the camera
then indicates the point which should be at the center of the
mounting place.

The  scanner has an off-center pivot on the camera mounting

platform which allows the camera tilt angle to be adjusted

from 10 degrees above the horizon line to 90 degrees below,
or from 10 degrees below the horizon line to 90 degrees
above depending on camera mounting (see Figure 3). To

adjust camera tilt angle at the pivot point, loosen the hex-head

screws (5 on Figure 2) on each side of the camera mounting

bracket and tilt the bracket to the desired position. Retighten

the two screws firmly. The 

 Series units have an

additional pan head screw on each side of the bracket.
Loosen for adjustment, then retighten.

OPERATION

Scanners used with a line cord option 

 do not use

a control unit. They operate automatically when connected
to the appropriate supply circuit. Other units are energized
through the main power switch on the control unit. For de-
tailed operating instructions refer to the 

 instruction

sheet supplied with scanner control.   

MAINTENANCE

These scanners are permanently lubricated and do not re-
quire regular maintenance.

REPAIR

Repairs should be attempted only by skilled personnel in an

adequately equipped facility. See Figure 4 through 

 for

Schematic Diagrams and Replacement Parts List.

4

X328-885

Summary of Contents for V3200AP Series

Page 1: ...g respectively when mounted in either the upright or inverted positions Slow The scanners are energized using the appropriate control speed high torque drive motors with instant start stop units Refer...

Page 2: ...ed to 4 Follow Instructions All operating and use instructrons should be followed 5 Cleaning Unplug the scanner from the wall outlet before cleaning Do not use liquid cleaners or aerosol cleaners Use...

Page 3: ...Proper performance depends on secure fastening to a suitable mount with the camera correctly mounted and balanced on the unit The units are installed directly on Vicon V114WM or V 1600WM Wall Mounts...

Page 4: ...ch use will cause excessive wear on the iris mechanism as it constantly compensates for different light levels Use a l 4 20 screw and lockwasher to mount the camera To obtain the best balance this scr...

Page 5: ...Road Hilsea Portsmouth Hampshire PO3 5JP England 0705 665312 VICON INDUSTRIES INC Southeastern Regional Office 3010 Business Park Dr Ste B Norcross Atlanta Georgia 30071 404 449 0499 800 824 8479 You...

Page 6: ...Figure 4 Schematic Diagram V3200AP and V3200 24AP 4 I I I I I 3q 2 ELK I 5 K E Y I N G P I N I 6 I K E Y I N G P I N 7 Ll210 3080 03 2 4 V 1210 3080 02 2 3 0 V 1210 3080 01 ll5V 2 4 V I 12 MFD IOOV 4...

Page 7: ...0 24AP SWITCH 11 lSM2 T SUB MIN MICRO V32 O 24AP V32 1 OAP 1 UL CSA LISTED RATED 5A 250 VAC SWITCH 11 lSM2 T SUB MIN MICRO V3200AP V3200 24PS UL CAS LISTED RATED 5A 250 VAC MOTOR PAN 4 1 RPM 12OV ALL...

Reviews: